Mitsubishi Electric FR-A7AD Instruction Manual
Mitsubishi Electric FR-A7AD Instruction Manual

Mitsubishi Electric FR-A7AD Instruction Manual

Plug-in option 700 series

Advertisement

Quick Links

INVERTER
Plug-in option
FR-A7AD

INSTRUCTION MANUAL

High-speed analog output function
Digital output function
PRE-OPERATION
INSTRUCTIONS
INSTALLATION AND WIRING
PARAMETER LIST
HIGH-SPEED ANALOG OUTPUT
DIGITAL OUTPUT
1
2
3
4
5

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FR-A7AD

  • Page 1: Instruction Manual

    INVERTER Plug-in option FR-A7AD INSTRUCTION MANUAL PRE-OPERATION High-speed analog output function INSTRUCTIONS INSTALLATION AND WIRING Digital output function PARAMETER LIST HIGH-SPEED ANALOG OUTPUT DIGITAL OUTPUT...
  • Page 2: Safety Instructions

    Thank you for choosing this Mitsubishi Inverter plug-in option. SAFETY INSTRUCTIONS This Instruction Manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please 1. Electric Shock Prevention read this manual carefully to use the equipment to its optimum.
  • Page 3 2. Injury Prevention 3) Usage WARNING CAUTION • Do not modify the equipment. • The voltage applied to each terminal must be the ones • Do not perform parts removal which is not instructed in this specified in the Instruction Manual. Otherwise burst, damage, etc.
  • Page 4: Table Of Contents

    — CONTENTS — 1 PRE-OPERATION INSTRUCTIONS Inverter Model ............................1 Unpacking and Product Confirmation .....................2 1.2.1 Product confirmation............................2 Parts ..............................3 Specifications.............................4 2 INSTALLATION AND WIRING Pre-Installation Instructions ......................5 Installation Procedure ........................6 Wiring..............................8 3 PARAMETER LIST 4 HIGH-SPEED ANALOG OUTPUT Wiring Example ..........................12 Terminals ............................13 Calibration procedure........................14 4.3.1...
  • Page 5 5 DIGITAL OUTPUT Terminals ............................23 Output Signal List ..........................24...
  • Page 6: Pre-Operation Instructions

    PRE-OPERATION INSTRUCTIONS Inverter Model The inverter model numbers of 55K and 75K stated in this Instruction Manual differ according to -NA, -EC, -CH(T) versions. Refer to the following correspondence table for each inverter model. (Refer to the Instruction Manual of each inverter for the inverter model.) For example, "for the 75K or higher"...
  • Page 7: Unpacking And Product Confirmation

    PRE-OPERATION INSTRUCTIONS Unpacking and Product Confirmation Take the plug-in option out of the package, check the product name, and confirm that the product is as you ordered and intact. This product is a plug-in option for the FR-A700 series manufactured in December 2011 or later. Check the SERIAL number specified on the inverter rating plate or package.
  • Page 8: Parts

    PRE-OPERATION INSTRUCTIONS Parts Mounting Terminal Rear view Front view hole block Mounting Switch for manufacturer Connector hole Mounting hole setting Connect to the inverter Do not change from initially- option slot set status (OFF: (Refer to page 6) Terminal layout...
  • Page 9: High-Speed Analog Output

    PRE-OPERATION INSTRUCTIONS 1.4 Specifications (1) Output signals High-speed analog output (across the terminal 5’s and the terminals DA2 to DA5), 0VDC to ±10VDC (12-bit output resolution) Digital output (across the terminal 5’s and the terminals DD0 to DD3), 3V to 6V for HI, 0V to 2V for LOW (2) Output accuracy (reference value) ±10% of the full-scale output value.
  • Page 10: Installation And Wiring

    INSTALLATION AND WIRING Pre-Installation Instructions Make sure that the input power of the inverter is off. CAUTION With input power on, do not install or remove the plug-in option. Otherwise, the inverter and plug-in option may be damaged. Static electricity in your body must be discharged before you touch the product. Otherwise the product may be damaged.
  • Page 11: Installation Procedure

    INSTALLATION AND WIRING Installation Procedure 1)Remove the inverter front cover. 2)Mount the hex-head screw for option mounting into the inverter screw hole (on earth plate). (size 5.5mm, tightening torque 0.56N⋅m to 0.75N⋅m) Screw hole for 3)Securely fit the connector of the plug-in option mounting option to the inverter connector along Inverter side...
  • Page 12 INSTALLATION AND WIRING CAUTION Only one type of option per inverter may be used. When two or more options are mounted, priority is in • order of inverter option connectors 1, 2 and 3, the options having lower priority are inoperative. When the inverter cannot recognize that the option is mounted due to improper •...
  • Page 13: Wiring

    INSTALLATION AND WIRING Wiring (1) Untwist the twisted pair shielded cables after stripping its sheath. Shield Also, perform protective treatment of the shield to ensure that it will not (perform protective treatment) make contact with the conductive area. Sheath Strip off the sheath about the size as in the below figure. If the length of Twisted pair the sheath pealed is too long, a short circuit may occur among shielded cable...
  • Page 14 INSTALLATION AND WIRING REMARKS • Information on blade terminals Commercially available product examples (as of Jan. 2010) Wire Size Blade Terminal Model Terminal Manufacturer Screw Size With insulation sleeve Without insulation sleeve Phoenix Contact 0.3, 0.5 AI 0,5-6WH A 0,5-6 Co.,Ltd.
  • Page 15 INSTALLATION AND WIRING (3) For wiring of the inverter which has one front cover, route wires between the control circuit terminal block and front cover. If cables can not be routed between the control circuit terminal block and front cover due to the increased number of cables, remove a hook of the front cover and use a space become available.
  • Page 16: Parameter List

    PARAMETER LIST When the FR-A7AD is mounted on the inverter, the following parameters are extended. Minimum Refer Parameter Initial Name Setting Range Setting Number alue Increments Page DA2 output selection 1 to 3, 5 to 14, 17 to 18, 21, 24,...
  • Page 17: High-Speed Analog Output

    Thus, high-speed monitoring is available with these terminals. (Refer to page 19 for high-speed monitoring.) * Terminals provided differ according to the inverter. Connect the voltmeter as shown below: Inverter FR-A7AD (Voltmeter) 0 to 10VDC DA2 to DA5 CAUTION • The wiring length between the FR-A7AD and the voltmeter should be 30m maximum.
  • Page 18: Terminals

    HIGH-SPEED ANALOG OUTPUT 4.2 Terminals Terminal Terminal Name Description Symbol Voltage output Connect a DC voltmeter (±10VDC). terminal Common terminals for DA2 to DA5 and DD0 to DD3. Common terminal These terminal 5’s are connected with the terminal 5 of the inverter. Used for digital output function.
  • Page 19: Calibration Procedure

    HIGH-SPEED ANALOG OUTPUT 4.3 Calibration procedure 4.3.1 Calibration of voltmeter If a voltmeter is deviated, it can be calibrated at 0V or full-scale voltage (10V) output of the terminals DA2 to DA5. (1) Calibration at 0V output Turning ON the X83 turns ON the Y83. In the initial status, 0V calibration is performed At least 20ms required at power OFF →...
  • Page 20 HIGH-SPEED ANALOG OUTPUT CAUTION • Keep the X83 signal ON for 20ms or longer. Otherwise, calibration may not be performed. • When the X83 signal is assigned, 0V calibration is not performed at power ON and at inverter reset. If power is turned OFF while the X83 is assigned, a 0V-calibrated value returns back to the logical value because the inverter does not save such calibrated values.
  • Page 21 Pr.900. (Terminal priority: DA2 DA5) • Calibration priority with Pr.900 is as follow when using FR-A7AY or FR-A7AZ in combination with FR-A7AD and "21" is set in Pr.310 Analog meter voltage output selection (FR-A7AY), Pr.838 DA1 terminal function selection (FR- A7AZ), Pr.525, Pr.527, Pr.529, and Pr.531.
  • Page 22: Monitor Setting

    HIGH-SPEED ANALOG OUTPUT 4.3.2 Monitor setting To output a monitored result as an analog output, set the values shown below in Pr.525 (terminal DA2), Pr.527 (terminal DA3), Pr.529 (terminal DA4), or Pr.531 (terminal DA5). For details about the monitored items selected with the setting values "1 to 53", refer to the description of Pr.54 FM/CA terminal function selection and Pr.158 AM terminal function selection in the Instruction Manual of the inverter.
  • Page 23 HIGH-SPEED ANALOG OUTPUT Setting Types of Monitor Increments Full Scale Value Motor load factor 0.1% 200% Torque command 0.1% Pr.866 Torque current command 0.1% Pr.866 Motor output 0.01kW/0.1kW Rated motor current Torque monitor (power driving/ — Pr.866 regeneration switchover) Motor temperature 1°C Pr.751 Changeable by...
  • Page 24 HIGH-SPEED ANALOG OUTPUT Types of Setting Increments Full Scale Value Description Monitor Output frequency 0.01Hz Pr.55 Displays the inverter output frequency. U-phase output 0.01A/0.1A Displays the U-phase output current. *8, *9 Pr.56 × current V-phase output 0.01A/0.1A Displays the V-phase output current. Pr.56 ×...
  • Page 25 HIGH-SPEED ANALOG OUTPUT Types of Setting Increments Full Scale Value Description Monitor Displays the input voltage to the terminal 1 Terminal 1 0.1% 100% (displays 100% for 10V (fixed)) Displays the inverter output frequency (0V to Output frequency 0.01Hz Pr.55 +10V during forward rotation, 0V to -10V *7, *8, *9 during reverse rotation)
  • Page 26: Scale Setting

    HIGH-SPEED ANALOG OUTPUT 4.3.3 Scale setting The scale of output voltage can be adjusted with Pr.526 (terminal DA2), Pr.528 (terminal DA3), Pr.530 (terminal DA4), and Pr.532 (terminal DA5). (Setting range: 1% to 400%) Use this function when you need to change the scale of the monitor because the full scale value is not changeable.
  • Page 27: Instructions

    HIGH-SPEED ANALOG OUTPUT 4.4 Instructions (1) A voltmeter having smaller internal impedance than the value indicated in the Specifications (page 4) may not deflect to full-scale and may not be calibrated. (2) To calibrate a voltmeter, of which full scale is less than 10VDC, disconnect the voltmeter first. Then, set terminal DA2 to DA5 outputs to the smallest values (set scale ratios to Pr.526, Pr.528, Pr.530, and Pr.532) according the voltmeter, and reconnect the voltmeter.
  • Page 28 DIGITAL OUTPUT 5.1 Terminals Use Pr.533 to Pr.536 to output the signals (RUN, SU, etc.), which are provided in the inverter as standard, as digital signals (0V, 5V). Terminal Terminal Name Description Symbol Use Pr. 533 to assign functions. Use Pr. 534 to assign functions. Digital output terminals Use Pr.
  • Page 29: Output Signal List

    DIGITAL OUTPUT 5.2 Output Signal List Use Pr.533 (terminal DD0), Pr. 534 (terminal DD1), Pr. 535 (terminal DD2), and Pr. 536 (terminal DD3) to output different signals as digital signals. For details of signal definitions, refer to Pr. 190 to Pr. 196 (Output terminal function selection) of Instruction manual of the inverter.
  • Page 30 DIGITAL OUTPUT Signal Terminal Setting Function Setting Function Name Name Y88 Cooling fan life Y89 Inrush current limit circuit life Y90 Life alarm Y91 Fault output 3 (power off signal) Y92 Energy saving average value updated timing Y93 Current average monitor signal ALM2 Fault output 2 Y95 Maintenance timer signal Outputs the different terminal statuses of...
  • Page 31 MEMO...
  • Page 32 MEMO...
  • Page 33 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date *Manual Number Revision First edition Nov. 2011 IB(NA)-0600475ENG-A IB(NA)-0600475ENG-A...
  • Page 34 INVERTER HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN IB(NA)-0600475ENG-A (1111) MEE Printed in Japan Specifications subject to change without notice.