Display Of The Life Of The Inverter Parts (Pr. 255 To Pr. 259) - Mitsubishi Electric FR-A740-00023 Instruction Manual

Fr-a700 series
Table of Contents

Advertisement

Useful functions

4.26.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259)

Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit
circuit can be diagnosed by monitor.
When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault.
(Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated
theoretically.)
For the life check of the main circuit capacitor, the alarm signal (Y90) will not be output if a measuring method of
(4) is not performed.
Parameter
Name
Number
255
Life alarm status display
Inrush current limit circuit
256
life display
Control circuit capacitor life
257
display
Main circuit capacitor life
258
display
Main circuit capacitor life
259
measuring
374
Initial Value
Setting Range
0
(0 to 15)
100%
(0 to 100%)
100%
(0 to 100%)
100%
(0 to 100%)
0, 1
0
(2, 3, 8, 9)
Description
Display whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each
parts of the inrush current limit circuit has
reached the life alarm output level or not.
Reading only
Display the deterioration degree of the inrush
current limit circuit. Reading only
Display the deterioration degree of the control
circuit capacitor. Reading only
Display the deterioration degree of the main
circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Setting "1" and switching the power supply off
starts the measurement of the main circuit
capacitor life.
When the Pr. 259 value is "3" after powering on
again, the measuring is completed. Read the
deterioration degree in Pr. 258.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents