Torque control by real sensorless vector control
4.5.6

Gain adjustment of torque control (Pr. 824, Pr. 825, Pr. 834, Pr. 835)

Although stable operation is possible with the initial value, make adjustment when any of such phenomena as
Pr.822
unusual motor and machine vibration/noise and overcurrent has occurred.
page 279
Pr.826
page 279
Parameter
Pr.832
Number
page 279
Pr.836
824
Torque control P gain 1
page 279
Torque control integral
825
time 1
834
Torque control P gain 2
Torque control integral
835
time 2
(1) Adjustment of current loop proportional (P) gain
⋅ For general adjustment, make setting within the range 50 to 200% as a guideline.
⋅ Set the proportional gain for torque control.
⋅ Increasing the value improves trackability in response to a current command change and reduces current variation
with disturbance. However, a too large gain will cause instability, generating harmonic torque pulsation.
(2) Adjustment of current control integral time
⋅ Set the integral time of current control during torque control.
⋅ A small value enhances the torque response level, but a too small value will cause current fluctuation.
⋅ Decreasing the value shortens the time taken to return to the original torque if current variation with disturbance
occurs.
(3) Use multiple gains
⋅ When you want to change the gain according to applications, switch multiple motors with one inverter, etc., use
Torque control P gain 2 and Torque control integral time 2 .
⋅ Pr. 834 Torque control P gain 2 and Pr. 835 Torque control integral time 2 are valid when the RT signal is on.
REMARKS
⋅ The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 225.)
⋅ The RT signal is assigned to the terminal RT in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal function
selection) , you can assign the RT signal to the other terminal.
126
Name
Initial Value
100%
5ms
9999
9999
Setting
Range
Set the current loop proportional gain.
0 to 200%
100% is equivalent to 2000rad/s.
0 to 500ms
Set the current loop integral compensation time.
Set the current loop proportional gain when the RT
0 to 200%
signal is on.
9999
Without torque control P gain 2 function
Set the current loop integral compensation time when
0 to500ms
the RT signal is on.
9999
Without torque control integral time 2 function