Starting Frequency And Start-Time Hold Function (Pr. 13, Pr. 571) - Mitsubishi Electric FR-A720-0.4K Instruction Manual

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Setting of acceleration/deceleration time
and acceleration/deceleration pattern

4.12.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571)

You can set the starting frequency and hold the set starting frequency for a certain period of time.
Pr.12
Set these functions when you need the starting torque or want to smooth motor drive at a start.
page 194
Pr.14
page 157
Parameter
Pr.569
Number
page 144
Pr.574
page 191
13
Starting frequency
571
Holding time at a start
Output
frequency
(Hz)
60
Pr.13
0
Forward
rotation
CAUTION
The inverter will not start if the frequency setting signal is less than the value set in Pr. 13.
For example, when 5Hz is set in Pr. 13, the motor will not start running until the frequency setting signal reaches 5Hz.
Output
frequency
(Hz)
60
Pr.13
0
Pr.571 setting time
Forward
rotation
CAUTION
⋅ When the start signal was turned off during start-time hold, deceleration is started at that point.
⋅ At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold function is
invalid.
Note that when Pr. 13 is set to any value lower than Pr. 2 Minimum frequency, simply turning on the start signal will
run the motor at the preset frequency even if the command frequency is not input.
♦ Parameters referred to ♦
Pr. 2 Minimum frequency
170
Name
Time
ON
Time
ON
Refer to page 153
Initial Value
Setting Range
0.5Hz
0 to 60Hz
0.0 to 10.0s
9999
9999
(1) Starting frequency setting (Pr. 13)
⋅ Frequency at start can be set in the range 0 to 60Hz.
⋅ You can set the starting frequency at which the start signal is
turned on.
(2) Start-time hold function (Pr. 571)
⋅ This function holds the time set in Pr. 571 and the output
frequency set in Pr. 13 Starting frequency.
⋅ This function performs initial excitation to smooth the motor drive
at a start.
REMARKS
When Pr. 13 = "0Hz", the starting frequency is held at 0.01Hz.
CAUTION
Description
Frequency at start can be set in the
range 0 to 60Hz.
You can set the starting frequency at
which the start signal is turned on.
Set the holding time of Pr. 13 Starting
frequency.
Holding function at a start is invalid