CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
⋅ One function can be assigned to two or more terminals. In this case, the terminal inputs are ORed.
⋅ The priorities of the speed commands are in order of jog, multi-speed setting (RH, RM, RL, REX) and PID (X14).
⋅ When the X10 signal (FR-HC, FR-CV connection - inverter operation enable signal) is not set or when the PU operation
external interlock (X12) signal is not assigned at the Pr. 79 Operation mode selection setting of "7", the MRS signal shares this
function.
⋅ Use common terminals to assign multi-speeds (speed 7) and remote setting. They cannot be set individually.
(Common terminals are used since these functions are designed for speed setting and need not be set at the same time.)
⋅ When V/F switching (X18) signal and load pattern selection forward rotation reverse rotation boost (X17) signal are not
assigned, the RT signal shares this function. (Pr. 81 Number of motor poles = "12, 14, 16, 18, 20")
In this case, V/F control is controlled by the second function.
(2) Response time of each signal
⋅ The response time of the X10 signal is within 2ms. However, when the X10 signal is not assigned at the Pr. 30
Regenerative function selection setting of "2" (FR-HC, MT-HC/FR-CV connection), the response time of the MRS
signal is within 2ms.
Pr. 17 MRS input selection is made invalid.
Pr. 30
MRS
Setting
Assignment
×
2
×
Other than 2
Response Time
X10
Assignment
MRS
×
Within 2ms
Within 20ms
×
Within 20ms
Within 20ms
Function assignment of external terminal and control
Pr. 17
X10
Invalid
Within 2ms
Within 2ms
Valid
Valid
Valid
4
223

Advertisement

Table of Contents