Selection of operation mode and operation location
Pr. 338 Communication operation command
Operation
Location
Pr. 339 Communication speed command
Selection
42
X42
Torque bias selection 1
43
X43
Torque bias selection 2
44
X44
P/PI control switchover
60
STF
Forward rotation command
61
STR
Reverse rotation command
62
RES
Reset
63
PTC
PID forward action switchover
64
X64
PID forward action switchover
65
X65
PU-NET operation switchover
External-NET operation
66
X66
switchover
67
X67
Command source switchover
Conditional position pulse
68
NP
train sign
Conditional position droop
69
CLR
pulse clear
DC feeding operation
70
X70
permission
71
X71
DC feeding cansel
[Explanation of table]
External
: Control is valid only from external terminal signal.
NET
: Control only from communication is valid
Combined
: Control is valid from either of external terminal and communication.
: Control is invalid from either of external terminal and communication.
Compensation : Control by signal from external terminal is only valid when Pr. 28 Multi-speed input compensation selection = "1"
REMARKS
⋅ The control source of communication is as set in Pr. 550 and Pr. 551.
(6) Switching of command source by external terminal (X67)
⋅ In network operation mode, the command source switching signal (X67) can be used to switch the operation
command source and speed command source. This signal can be utilized to control the signal input from both the
external terminal and communication.
⋅ Set "67" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the X67 signal to the external
terminal.
⋅ When the X67 signal is off, the operation command source and speed command source are external.
X67 Signal State
No signal assignment
ON
OFF
REMARKS
⋅ The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched
during operation.
⋅ When the X67 signal is off, a reset via communication is disabled.
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
♦ Parameters referred to ♦
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
308
source
0: NET
source
NET
Operation Command Source
According to Pr. 338
Operation is valid only from external terminal signal.
Refer to page 165.
Refer to page 165.
Refer to page 295.
0: NET
1: External
1:External 2:External 0: NET
NET
NET
NET
NET
NET
External
External
External
NET
External
External
External
External
External
NET
NET
Speed Command Source
According to Pr. 339
Remarks
1:External 2:External
External
External
External
External
External
External
External
External