Noise and leakage currents
1) Calculation of equivalent capacity P0 of harmonic generating equipment
The "equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic
generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than
the limit in Table 3, harmonics must be calculated with the following procedure:
P0 = Σ (Ki × Pi) [kVA]
Ki: Conversion factor(According to Table 2)
Pi: Rated capacity of harmonic generating equipment
i : Number indicating the conversion circuit type
2) Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage) × operation
ratio × harmonic content
⋅ Operation ratio: Operation ratio = actual load factor × operation time ratio during 30 minutes
⋅ Harmonic content: Found in Table 4.
Table 5 Rated capacities and outgoing harmonic currents of inverter-driven motors
Rated Current
Applied
(A)
Motor
(kW)
200V
400V
0.4
1.61
0.81
0.75
2.74
1.37
1.5
5.5
2.75
2.2
7.93
3.96
3.7
13.0
6.50
5.5
19.1
9.55
7.5
25.6
12.8
11
36.9
18.5
15
49.8
24.9
18.5
61.4
30.7
22
73.1
36.6
30
98.0
49.0
37
121
60.4
45
147
73.5
55
180
89.9
Rated Current
Applied
(A)
Motor
(kW)
200V
400V
75
245
123
90
293
147
110
357
179
132
216
160
258
220
355
250
403
280
450
315
506
355
571
400
643
450
723
500
804
60
[kVA]
*
Fundamental
Wave Current
Rated
Converted
Capacity
from 6.6kV
(kVA)
(mA)
49
0.57
83
0.97
167
1.95
240
2.81
394
4.61
579
6.77
776
9.07
1121
13.1
1509
17.6
1860
21.8
2220
25.9
2970
34.7
3660
42.8
4450
52.1
5450
63.7
Fundamental
Wave Current
Rated
Converted
Capacity
from 6.6kV
(kVA)
(mA)
7455
87.2
8909
104
10848
127
13091
153
15636
183
21515
252
24424
286
27273
319
30667
359
34606
405
38970
456
43818
512
48727
570
* Rated capacity: Determined by the capacity of the applied motor and
found in Table 5. It should be noted that the rated capacity used here
is used to calculate generated harmonic amount and is different from
the power supply capacity required for actual inverter drive.
Outgoing Harmonic Current Converted from 6.6kV (mA)
(No reactor, 100% operation ratio)
5th
7th
11th
31.85
20.09
4.165
53.95
34.03
7.055
108.6
68.47
14.20
156.0
98.40
20.40
257.1
161.5
33.49
376.1
237.4
49.22
504.4
318.2
65.96
728.7
459.6
95.29
980.9
618.7
128.3
1209
762.6
158.1
1443
910.2
188.7
1931
1218
252.5
2379
1501
311.1
2893
1825
378.3
3543
2235
463.3
Outgoing Harmonic Current Converted from 6.6kV (mA)
(With DC reactor, 100% operation ratio)
5th
7th
11th
2237
969
626
2673
1158
748
3254
1410
911
3927
1702
1100
4691
2033
1313
6455
2797
1807
7327
3175
2052
8182
3545
2291
9200
3987
2576
10382
4499
2907
11691
5066
3274
13146
5696
3681
14618
6335
4093
13th
17th
19th
3.773
2.107
1.519
6.391
3.569
2.573
12.86
7.181
5.177
18.48
10.32
7.440
30.34
16.94
12.21
44.58
24.90
17.95
59.75
33.37
24.06
86.32
48.20
34.75
116.2
64.89
46.78
143.2
79.98
57.66
170.9
95.46
68.82
228.7
127.7
92.07
281.8
157.4
113.5
342.7
191.4
138.0
419.7
234.4
169.0
13th
17th
19th
373
350
239
445
419
285
542
510
347
655
615
419
782
735
500
1076
1011
688
1221
1148
782
1364
1282
873
1533
1441
981
1730
1627
1107
1949
1832
1247
2191
2060
1402
2436
2290
1559
23rd
25th
1.274
0.882
2.158
1.494
4.342
3.006
6.240
4.320
10.24
7.092
15.05
10.42
20.18
13.97
29.15
20.18
39.24
27.16
48.36
33.48
57.72
39.96
77.22
53.46
95.16
65.88
115.7
80.10
141.7
98.10
23rd
25th
224
164
267
196
325
239
393
288
469
344
645
473
733
537
818
600
920
675
1038
761
1169
857
1315
964
1462
1072