4.26.4 Current average value monitor signal (Pr. 555 to Pr. 557)

The average value of the output current during
constant speed operation and the maintenance
timer value are output as a pulse to the current
average value monitor signal (Y93).
The pulse width output to the I/O module of the
programmable controller etc. can be used as a
guideline due to abrasion of machines and
elongation of belt and for aged deterioration of
devices to know the maintenance time.
The current average value monitor signal (Y93) is
output as pulse for 20s as 1 cycle and repeatedly
output during constant speed operation.
Parameter
Name
Number
555
Current average time
556
Data output mask time
Current average value
557
monitor signal output
reference current
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
1) Data output mask time
When the speed has changed to constant
from acceleration/deceleration, Y93 signal is
not output for Pr. 556 time.
2) Start pulse
Output as Hi pulse shape for 1s (fixed)
The output currents are averaged during the time
period set in Pr.555.
3) Output current average value pulse
The averaged current value is output as low pulse shape for
0.5 to 9s (10 to 180%) during start pulse output.
Signal output time=
⋅ The pulse output of the current average value monitor signal (Y93) is shown above.
⋅ For the terminal used for the Y93 signal output, assign the function by setting "93" (positive logic) or "193" (negative
logic) to any of Pr. 190 to Pr. 194 (output terminal function selection). (The function cannot be assigned to Pr. 195 ABC1
terminal function selection and Pr. 196 ABC2 terminal function selection.)
(1) Setting of Pr. 556 Data output mask time
The output current is unstable (transient state) right after the operation is changed from the acceleration/
deceleration state to the constant speed operation. Set the time for not obtaining (mask) transient state data in Pr.
556.
(2) Setting of the Pr. 555 Current average time
The average output current is calculated during Hi output of start pulse (1s). Set the time taken to average the
current during start pulse output in Pr. 555.
390
Initial Value
1s
0s
55K or lower
Rated inverter
current
75K or higher
From acceleration to constant speed operation
Y93 signal
output current average value (A)
5s
Pr. 557 (A)
Programmable controller
maintenance
time
parts have
reached their life
Setting Range
0.1 to 1.0s
0.0 to 20.0s
0 to 500A
0 to 3600A
Output
frequency
1 cycle (20s)
Next cycle
5) End pulse
output as low pulse
shape for 1 to 16.5s
4) Maintenance timer pulse
The maintenance timer value (Pr. 503) is output
as Hi output pulse shape for 2 to 9s (16000h to
72000h).
Pr. 503
Signal output time=
40000h
Output
Input
unit
unit
Inverter
Description
Set the time taken to average
the current during start pulse
output (1s).
Set the time for not obtaining
(mask) transient state data.
Set the reference (100%) for
outputting the signal of the
current average value.
Time
100h
5s