Mitsubishi Electric FR-A720-0.4K Instruction Manual page 314

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

b) Method to adjust any point without application of a voltage (current) across terminals 1 and 5(4 and 5)
(To change from 8V (80%) to 10V (100%))
Operation
1.
Confirm the RUN indicator and operation mode
indicator.
The inverter must be at a stop.
The inverter must be in the PU operation
mode. (Using
)
2.
Press
to choose the parameter
setting mode.
3.
Turn
until
4.
Press
to display
5.
Turn
until
(
appears. Set to C19 Terminal 1 gain (torque).
6.
Press
to display the analog voltage
(current) value (%).
7.
Turn
to set the gain voltage (%).
"0V (0mA) equals to 0%, 10V (5V,
20mA) to 100%"
REMARKS
The present setting at the instant of turning
is displayed.
8.
Press
to set.
REMARKS
You can check the current torque setting bias/gain setting by pressing
You cannot check after performing operation in step 7.
appears.
.
)
Flicker...Parameter setting complete!!
By turning
, you can read another parameter.
Press
to return to the
Press
twice to show the next parameter (
Frequency/torque setting by analog
input (terminal 1, 2, 4)
Display
The parameter
number read
previously appears.
C0 to C41
setting
is enabled.
Terminal 1 input Terminal 4 input
Analog voltage (current)
value (%) across terminals 1 and 5
(across terminals 4 and 5)
The gain torque is
reached when the analog
voltage (current) value across
terminals 1 and 5 (across terminals
4 and 5) is 100%.
Terminal 1 input Terminal 4 input
(Adjustment completed)
display (step 4).
).
after step 6.
4
303