Mitsubishi Electric FR-A720-0.4K Instruction Manual page 197

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Selection and protection of a motor
(5) External thermal relay input (OH signal)
Thermal relay protector
Inverter
Motor
U
V
IM
W
OH
SD
External thermal relay input
connection example
Inverter
*
PC
G1
2W1kΩ
CS(OH)
G2
SD
Connection of the thermal
protector of the SF-V5RU
CAUTION
⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Set
parameters after confirming the function of each terminal.
(6) PTC thermistor input (PTC signal)
Inverter
U
AU
V
W
PTC
AU(PTC)
SD
PTC thermistor input connection example
Built-in PTC thermistor of the motor can be input to the PTC signal (AU terminal).
⋅ For the terminal used for PTC signal input, assign the function by setting "63" in Pr. 184 AU terminal function selection
and also set the AU/PTC switchover switch to the PTC terminal function. (The initial setting is the AU terminal
function.)
⋅ If a motor overheat state is detected for more than 10s according to the input from the PTC thermistor, the inverter
trips and outputs the PTC thermal fault signal (E.PTC).
⋅ The input specifications of the PTC thermistor
are shown on the right.
CAUTION
⋅ When the PTC signal was not assigned to Pr. 184 and the AU/PTC switchover switch was set to the PTC terminal function, the
function assigned to the AU terminal is always OFF. Reversely, when the PTC signal was assigned to Pr. 184 and the AU/PTC
switchover switch was set to the AU terminal function, a PTC thermal fault (E.PTC) occurs since the function is always in a
motor overheat state.
⋅ When you want to input a current, assign the AU signal to the other signal.
⋅ When terminal assignment is changed, the other functions may be affected. Set parameter after confirming the function of the
AU terminal.
♦ Parameters referred to ♦
Pr. 71 Applied motor
Refer to page 187
Pr. 72 PWM frequency selection
Pr. 178 to Pr. 189 (input terminal function selection)
Pr. 190 to Pr. 196 (output terminal function selection)
Specifications of the AU terminal
186
⋅ To protect the motor against overheat, use the OH signal when using an external
thermal relay or the built-in thermal protector of the motor.
⋅ When the thermal relay operates, the inverter trips and outputs the fault signal
(E.OHT).
⋅ For the terminal used for OH signal input, assign the function by setting "7" in any
of Pr. 178 to Pr. 189 (input terminal function selection)
⋅ A thermal protector is provided for a vector control dedicated motor (SF-V5RU).
* Assign OH (external thermal input) signal to the CS terminal.
SF-V5RU
(Pr. 186 = "7")
Connect a 2W1kΩ resistor between the terminal PC and
CS(OH).
Install the resistor pushing it against the bottom part of the
terminal block so as to avoid a contact with other cables.
page
Refer to
selection.
Motor
Refer to page 284
Refer to page 231
Refer to page 239
Refer to page 25
231 for details of Pr. 186 CS terminal function
AU
PTC
AU/PTC switchover switch
Factory-set to "AU".
Set to the "PTC" position to
validate the PTC signal input.
Motor Temperature
Normal
Boundary
Overheat
Inverter
PTC Thermistor Resistance Value (Ω)
0 to 500
500 to 4k
4k or higher
CS(OH)
PC
Control circuit
terminal block
Resistor (2W1kΩ)