Mitsubishi Electric FR-A720-0.4K Instruction Manual page 190

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

CAUTION
⋅ When the acceleration/deceleration time (Pr. 7, Pr. 8, etc.) setting under Real sensorless vector control or vector control is 0s,
the S-pattern acceleration/deceleration A to D (Pr. 29 = "1, 2, 4, 5") is linear acceleration/deceleration.
⋅ Set linear acceleration/deceleration (Pr. 29 = "0 (initial value)") when torque control is exercised under Real sensorless vector
control or vector control. When acceleration/deceleration patterns other than the linear acceleration/deceleration are selected,
the protective function of the inverter may function.
♦ Parameters referred to ♦
Pr. 3 Base frequency
Refer to page 159
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 20 Acceleration/deceleration reference frequency
Pr. 178 to Pr. 189 ( Input terminal function selection )
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
Refer to page 231
Refer to page 172
4
179