Mitsubishi Electric FR-A720-0.4K Instruction Manual page 368

Fr-a700 series
Hide thumbs Also See for FR-A720-0.4K:
Table of Contents

Advertisement

Parameter
Parameters Register
41000 to
Refer to the parameter list (page 71) for
0 to 999
41999
the parameter names.
Terminal 2 frequency setting bias
C2(902)
41902
(frequency)
Terminal 2 frequency setting bias
42092
(analog value)
C3(902)
Terminal 2 frequency setting bias
43902
(terminal analog value)
Terminal 2 frequency setting gain
125(903)
41903
(frequency)
Terminal 2 frequency setting gain
42093
(analog value)
C4(903)
Terminal 2 frequency setting gain
43903
(terminal analog value)
Terminal 4 frequency setting bias
C5(904)
41904
(frequency)
Terminal 4 frequency setting bias
42094
(analog value)
C6(904)
Terminal 4 frequency setting bias
43904
(terminal analog value)
Terminal 4 frequency setting gain
126(905)
41905
(frequency)
Terminal 4 frequency setting gain
42095
(analog value)
C7(905)
Terminal 4 frequency setting gain
43905
(terminal analog value)
C12(917)
41917
Terminal 1 bias frequency (speed)
42107
Terminal 1 bias (speed)
C13(917)
Terminal 1 bias (speed)
43917
(terminal analog value)
C14(918)
41918
Terminal 1 gain frequency (speed)
42108
Terminal 1 gain (speed)
C15(918)
Terminal 1 gain (speed)
43918
(terminal analog value)
Terminal 1 bias command (torque/
C16(919)
41919
magnetic flux)
42109
Terminal 1 bias (torque/magnetic flux)
C17(919)
Terminal 1 bias (torque/magnetic flux)
43919
(terminal analog value)
Terminal 1 gain command (torque/
C18(920)
41920
magnetic flux)
42110
Terminal 1 gain (torque/magnetic flux)
C19(920)
Terminal 1 gain (torque/magnetic flux)
43920
(terminal analog value)
Terminal 4 bias command (torque/
C38(932)
41932
magnetic flux)
42122
Terminal 4 bias (torque/magnetic flux)
C39(932)
Terminal 4 bias (torque/magnetic flux)
43932
(terminal analog value)
Terminal 4 gain command (torque/
C40(933)
41933
magnetic flux)
42123
Terminal 4 gain (torque/magnetic flux)
C41(933)
Terminal 4 gain (torque/magnetic flux)
43933
(terminal analog value)
Parameter Name
Communication operation and setting
Read/Write
The parameter number + 41000 is the
Read/write
register number.
Read/write
The analog value (%) set to C3 (902) is
Read/write
read.
The analog value (%) of the voltage
Read
(current) applied to the terminal 2 is read.
Read/write
The analog value (%) set to C4 (903) is
Read/write
read.
The analog value (%) of the voltage
Read
(current) applied to the terminal 2 is read.
Read/write
The analog value (%) set to C6 (904) is
Read/write
read.
The analog value (%) of the current
Read
(voltage) applied to the terminal 4 is read.
Read/write
The analog value (%) set to C7 (905) is
Read/write
read.
The analog value (%) of the current
Read
(voltage) applied to the terminal 4 is read.
Read/write
Read/write
Analog value (%) set in C13 (917) is read.
Analog value (%) of the voltage applied to
Read
terminal 1 is read.
Read/write
Read/write
Analog value (%) set in C15 (918) is read.
Analog value (%) of the voltage applied to
Read
terminal 1 is read.
Read/write
Read/write
Analog value (%) set in C17 (919) is read.
Analog value (%) of the voltage applied to
Read
terminal 1 is read.
Read/write
Read/write
Analog value (%) set in C19 (920) is read.
Analog value (%) of the voltage applied to
Read
terminal 1 is read.
Read/write
Read/write
Analog value (%) set in C39 (932) is read.
Analog value (%) of the current (voltage)
Read
applied to terminal 4 is read.
Read/write
Read/write
Analog value (%) set in C41 (933) is read.
Analog value (%) of the current (voltage)
Read
applied to terminal 4 is read.
Remarks
357