Main circuit terminal specifications
• FR-A720-11K or higher, FR-A740-11K or higher
1) Remove the upper screws.
2) Remove the lower screws.
3) Pull the jumper toward you to
remove.
4) Connect the separate power supply
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
CAUTION
· When using separate power supply, always remove the jumper across terminals R/L1 and R1/L11 and across S/L2 and S1/L21.
The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
primary side of the MC.
· The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter capacity.
200V class
400V class
· If the main circuit power is switched OFF (for 0.1s or more) then ON again, the inverter resets and a fault output will not be held.
24
R1/
S1/
L11
L21 Power supply
R/L1S/L2 T/L3
MC
Main power supply
FR-A720-11K,
FR-A740-11K, 15K
Power supply
terminal block for
the control circuit
11K or lower
60VA
60VA
terminal block
for the control circuit
FR-A720-15K, 18.5K, 22K,
FR-A740-18.5K, 22K
15K
18.5K or higher
80VA
60VA
3)
Power supply terminal block
for the control circuit
R1/L11
S1/L21
1)
2)
4)
FR-A720-30K or higher,
FR-A740-30K or higher
80VA
80VA
U
V
W