Check

8. Check

Check No.01
Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, probe the faulty points.
Local
pressure
rise
[In cooling]
If the outdoor unit electronic
expansion valve is throttled:
(See *1.)
Rise in high
pressure
Faulty high
pressure
control
[In heating]
If the indoor unit electronic
expansion valve excessively
throttled:
(See *2.)
[In cooling]
High suction
air
temperature
of the
condenser
Degradation
in condensing
capacity
Excessive refrigerant charging
Improper model selection [In heating]
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for "subcooled degree control".
352
High pipe
resistance
Faulty outdoor
unit electronic
expansion valve
A temperature di f f e rence i n excess of 10°C
between the i n l e t and the outl e t i s deemed to be abnormal .
Faulty
control
Faulty indoor
unit electronic
expansion valve
Faulty
control
High suction air
temperature of
outdoor unit
High suction
air temperature
of indoor unit
Faulty suction air thermistor of indoor unit
[In heating]
High suction air temperature of outdoor unit
Faulty outdoor temperature thermistor of outdoor unit
Dirty condenser
Mixing of non-condensable gas
Decreased
fan airflow
rate
!Check to be sure the stop valve is open.
Stop valve closed
!Conduct visual checks for pipe conditions.
Bent or crashed pipe
Clogging of foreign
!Is there any temperature difference caused before
particles
!Are the coil resistance and insulation normal?
Faulty valve coil
Faulty valve body
!Are the electrical characteristics normal?
Faulty high pressure sensor
!Is the pressure value checked with the Service Checker
Faulty control PCB
!Are the coil resistance and insulation
Faulty valve coil
Faulty valve body
!Are the electrical characteristics normal?
Faulty high pressure sensor
!In the connector properly connected?
Faulty indoor unit
liquid pipe thermistor
!Is the pressure value checked with the Service
Faulty control PCB
Short circuit
High ambient temperature
Short circuit
High ambient temperature
!Is the heat exchanger clogged? (In cooling)
!Is air or else mixed in the refrigerant system?
Faulty fan
Decreased
motor
fan
output
Faulty control
PC board
(Including
capacity setting)
Dirty filter
High air
passage
resistance
Obstacle
!Refer to page 313.
!Is the indoor unit too small compared to
the large-sized outdoor unit?
SiENBE18-621
and after the filter or branch pipe.
corresponding to the measurement of the pressure sensor?
normal?
Are the thermistor resistance characteristics normal?
Checker corresponding to the measurement of the
pressure sensor?
!Is the suction air temperature not more than
46°C?
!Is the outdoor temperature not more than 46°C?
!Is the suction air temperature not more than 27°C?
!Is the indoor temperature not more than 27°C?
!Is the connector properly connected?
Are the thermistor resistance characteristics normal?
!Is the outdoor temperature not more than 16?CWB?
!Is the connector properly connected?
Are the thermistor resistance characteristics normal?
!Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
!If a spare PC board is mounted, is the
capacity setting properly made?
!Is the air filter clogged?
!Is there any obstacle in the air passage?
Troubleshooting