Swing Flap Motor Malfunction / Lock

A7
Remote Control
Display
Applicable
FHQ-BU
Models
Method of
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction
When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
Decision
motor is energized for a specified amount of time (about 30 seconds).
Conditions
" Failure of motor
Supposed
" Failure of microswitch
Causes
" Failure of connector connection
" Failure of indoor unit PCB