3. List of Malfunction Code

Malfunction
code
Indoor
A0
Error of external protection device
Unit
A1
PC board defect, E
A3
Malfunction of drain level control system (33H)
A5
Freeze-up protection or high pressure control
A6
Fan motor (MF) lock, overload
A7
Malfunction of swing flap motor (MA)
A9
Malfunction of electronic expansion valve (20E)
AF
Drain pump error
AJ
Malfunction of capacity setting
C4
Malfunction of thermistor (R2T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
C5
Malfunction of thermistor (R3T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
C7
Shutter drive motor / shutter limit switch abnormality
C9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
CA
Malfunction of thermistor for air outlet (loose
connection, disconnection, short circuit, failure)
CJ
Malfunction of thermostat sensor in remote control
Outdoor
E1
PC board defect, E
Unit
E2
Faulty BP unit PCB
E3
Actuation of high pressure switch
E4
Actuation of low pressure switch
E5
Compressor motor lock
E6
Standard compressor lock or over current
E7
Malfunction of outdoor unit fan motor
E9
Malfunction of moving part of electronic expansion
valve (Y1E~3E)
F3
Abnormal discharge pipe temperature
F6
Refrigerant overcharged
H3
Malfunction of high pressure switch
H4
Actuation of low pressure switch
H7
Abnormal outdoor fan motor signal
H9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
J0
Faulty BP liquid or gas pipe thermistor
J2
Current sensor malfunction
J3
Malfunction of discharge pipe thermistor (R2T) (loose
connection, disconnection, short circuit, failure)
J5
Malfunction of thermistor (R3T, R5T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
J6
Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
J7
Malfunction of liquid thermistor (R7T)
J8
Malfunction of thermistor (R7T) for oil equalizing pipe.
(loose connection, disconnection, short circuit,
failure)
J9
Malfunction of subcooling heat exchanger thermistor
(R6T)
JA
Malfunction of discharge pipe pressure sensor
JC
Malfunction of suction pipe pressure sensor
L0
Inverter system error
268
Malfunction contents
2
PROM defect
2
PROM defect
9: Blink 8: ON 7: OFF
Page Referred
RA Indoor
SkyAir
BP Unit
Unit
Indoor Unit
270
281
282
271
273, 274
285, 286
288
284
290
276
291
292
277
276
293
294
SiENBE18-621
Outdoor
Unit
300
307
301
308
310
312
313
314
316
317
318
302
319
320
321
322
323
324
325
Troubleshooting