Daikin FHQ35BVV1B Technical Data Manual
Hide thumbs Also See for FHQ35BVV1B:

Advertisement

technical data

FHQ-BVV1B
Wall Mounted Unit
Split
Sky Air

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FHQ35BVV1B

  • Page 1: Technical Data

    technical data FHQ-BVV1B Wall Mounted Unit Split Sky Air...
  • Page 2: Table Of Contents

    • Indoor Units • R-410A • FHQ-BVV1B TABLE OF CONTENTS FHQ-BVV1B Features ............. 2 Specifications .
  • Page 3: Features

    R - 4 • Slim unit with super silent and greater air flow • Daikin remote controls give you easy control at your fingertips. • Ideal for shops, restaurants or offices requiring maximum floor space • The wired remote control provides you with a schedule timer, for furniture, decorations and fittings enabling to program the air conditioning daily or weekly.
  • Page 4: Specifications

    • Indoor Units • R-410A • FHQ-BVV1B Specifications 2-1 FOR INDOOR UNITS ONLY FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B Nominal Input Cooling 0.111 0.111 0.115 0.117 0.135 0.144 2-2 TECHNICAL SPECIFICATIONS FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B Casing Colour White...
  • Page 5: Electrical Specifications

    • Indoor Units • R-410A • FHQ-BVV1B Specifications 2-2 TECHNICAL SPECIFICATIONS FHQ35BVV1B FHQ50BVV1B FHQ60BVV1B FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B Standard Item Installation and operation manual Accessories Quantity Item Paper pattern for installation Drain hose Clamp metal Insulation for fitting Sealing pad Clamps...
  • Page 6: Safety Device Settings

    • Indoor Units • R-410A • FHQ-BVV1B Safety device settings FHQ35∼60B Model Safety devices Fuse 250V 5A 250V 5A 250V 5A FHQ-B Off: 130 ±5 Off: 130 ±5 Off: 130 ±5 Fan motor thermal protector (°C) On: 83 ±20 On: 83 ±20 On: 83 ±20 3D006611M •...
  • Page 7: Options

    • Indoor Units • R-410A • FHQ-BVV1B Options FHQ35∼60B Name of option FHQ∼B Replacement long-life filter KAFJ501DA56 KAFJ501DA80 Drain up kit KDU50N60VE L-type piping kit (for upward direction) KHFP5MA35 KHFP5MA63 Remote control Wired type BRC1D528 Infrared type Heat pump BRC7EA63W Cooling only BRC7EA66 Central remote control...
  • Page 8: 4 Options

    • Indoor Units • R-410A • FHQ-BVV1B Options FHQ∼B Name of option Remark Replacement long-life filter KAF501DA80 KAF501DA112 KAF501DA160 Drain up kit KDU50N125VE L-type piping kit (for upward direction) KHFP5MA160 Remote control Wired type BRC1D528 Infrared type For Heat pump BRC7EA63W For cooling only BRC7EA66...
  • Page 9: Control Systems

    • Indoor Units • R-410A • FHQ-BVV1B Control systems BRC1D52 5 x 10 (Round end slit) 6.5 x 9 (Round end slit) HoleJ5 5 x 7 (Round end slit) Cover closed 3TW23651-2 Cover open • Split Sky Air • Indoor Units...
  • Page 10: Dimensional Drawing & Centre Of Gravity

    • Indoor Units • R-410A • FHQ-BVV1B Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing FHQ35B Position slit hole for taking out in piping back (View from the front) Hanging bolt (Hanging position) Position: hole of wall for taking out in piping back (View from the front) 30 or more 30 or more...
  • Page 11 • Indoor Units • R-410A • FHQ-BVV1B Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing FHQ60B Position slit hole for taking out in piping back (View from the front) (Hanging position) Hanging bolt Position: hole of wall for taking out in piping back (View from the front) 30 or more 30 or more...
  • Page 12 • Indoor Units • R-410A • FHQ-BVV1B Dimensional drawing & centre of gravity 6 - 1 Dimensional drawing FHQ100B Position slit hole for taking out in piping back (View from the front) Hanging bolt (Hanging position) Position: hole of wall for taking out in piping back (View from the front) 30 or more 30 or more...
  • Page 13: Piping Diagram

    • Indoor Units • R-410A • FHQ-BVV1B Piping diagram FHQ35∼125B Indoor heat exchanger Model FHQ35B FHQ50-60B 12.7 FHQ71,100,125B 15.9 Field pipingJA C1220T-O To outdoor unit Field pipingJB C1220-O Indoor unit Check valve Flare connection Screw connection Flange connection Pinched pipe Spinned pipe 4D037995F •...
  • Page 14: Wiring Diagram

    • Indoor Units • R-410A • FHQ-BVV1B Wiring diagram 8 - 1 Wiring diagram FHQ35∼60B Connecter discrimination colour for components. In case of simultaneous operation system. Connecter colour for components. Connecter colour for printed circuit board. Notes Indoor unit Indoor unit To outdoor (master) (slave)
  • Page 15: External Connection Diagram

    • Indoor Units • R-410A • FHQ-BVV1B Wiring diagram 8 - 2 External connection diagram NOTES Line voltage wiring Control circuit wiring All wiring, components and materials to be produced on the site must comply with the applicable local and national codes. Use copper conductors only.
  • Page 16: Sound Data

    • Indoor Units • R-410A • FHQ-BVV1B Sound data 9 - 1 Sound level data Sound pressure level 230V Sound power level Model 50Hz Measuring location (cooling/heating) (cooling/heating) (cooling/heating) (cooling/heating) FHQ35BUV1B 37/37 32/32 53/53 48/48 Location of microphone FHQ50BUV1B 38/38 33/33 54/54 49/49...
  • Page 17: Sound Pressure Spectrum

    • Indoor Units • R-410A • FHQ-BVV1B Sound data 9 - 2 Sound pressure spectrum FHQ35B FHQ50B H (230V) H (230V) L (230V) L (230V) approximate approximate threshold hearing threshold hearing for continuous for continuous noise noise 4D028280B 4D028281B Octave band center frequency (Hz) Octave band center frequency (Hz) NOTES NOTES...
  • Page 18 • Indoor Units • R-410A • FHQ-BVV1B Sound data 9 - 2 Sound pressure spectrum FHQ100B FHQ125B approximate threshold approximate threshold hearing for continuous hearing for continuous noise noise 4D028284B 4D028283B Octave band center frequency (Hz) Octave band center frequency (Hz) NOTES NOTES Operation sound is measured in an anechoic...
  • Page 19: Air Flow Pattern

    • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ35∼50B Cooling - air velocity distribution Air flow direction: horizontal FHQ35∼50B Cooling - air temperature distribution Air flow direction: horizontal 4D028550 • Split Sky Air • Indoor Units...
  • Page 20 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ60-71B Cooling - air velocity distribution Air flow direction: horizontal FHQ60-71B Cooling - air temperature distribution Air flow direction: horizontal 4D028551B • Split Sky Air • Indoor Units...
  • Page 21 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ100B Cooling - air velocity distribution Air flow direction: horizontal FHQ100B Cooling - air temperature distribution Air flow direction: horizontal 4D028552B • Split Sky Air • Indoor Units...
  • Page 22 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ125B Cooling - air velocity distribution Air flow direction: horizontal FHQ125B Cooling - air temperature distribution Air flow direction: horizontal 4D028553B • Split Sky Air • Indoor Units...
  • Page 23 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ35∼50B Heating - air velocity distribution Air flow direction: 45° (downward) FHQ35∼50B Heating - air temperature distribution Air flow direction: 45° (downward) 4D028554 • Split Sky Air • Indoor Units...
  • Page 24 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ60-71B Heating - air velocity distribution Air flow direction: 45° (downward) FHQ60-71B Heating - air temperature distribution Air flow direction: 45° (downward) 4D028555B • Split Sky Air • Indoor Units...
  • Page 25 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ100B Heating - air velocity distribution Air flow direction: 45° (downward) FHQ100B Heating - air temperature distribution Air flow direction: 45° (downward) 4D028556B • Split Sky Air • Indoor Units...
  • Page 26 • Indoor Units • R-410A • FHQ-BVV1B Air flow pattern FHQ125B Heating - air velocity distribution Air flow direction: 45° (downward) FHQ125B Heating - air temperature distribution Air flow direction: 45° (downward) 4D028557B • Split Sky Air • Indoor Units...
  • Page 27 Daikin Europe N.V. explicitly rejects any liability for any direct Daikin Europe N.V. is approved by LRQA for its Quality Daikin Europe N.V. is participating in the or indirect damage, In the broadest sense, arising from Management System in accordance with the ISO9001 EUROVENT Certification Programme.

This manual is also suitable for:

Fhq50bvv1bFhq60bvv1bFhq71bvv1bFhq100bvv1bFhq125bvv1b