Skyair Indoor Unit Inspection/Test Button - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiENBE18-621
2.2

SkyAir Indoor Unit INSPECTION/TEST Button

Explanation
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Indoor unit settings can be made
• Filter sign time
• Air flow direction
• Others
Depress Inspection/Test Operation button
for more than 4 seconds.
Press Inspection/Test Operation
button once.
Following codes can be checked.
• Malfunction codes
• Indoor model code
• Outdoor model code
Troubleshooting
Depress Inspection/Test Operation button
for more than 4 seconds.
Local
setting
mode
Normal
mode
After 10 seconds
Inspection
mode
Press Inspection/Test Operation
button once.
Service data can be obtained.
Service
• Malfunciton code history
• Temperature data of various sections
mode
Service settings can be made.
• Forced fan ON
• Air flow direction/volume setting
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes
Test
operation
Thermostat is forcibly turned on.
mode
Service Check Function
(V0815)
259

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents