Malfunction Of Moving Part Of Electronic Expansion Valve (Y1E, Y3E) - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
7.6
Malfunction of Moving Part of Electronic Expansion
Valve (Y1E, Y3E)
E9
Remote Control
Display
Applicable
AII outdoor unit models
Models
Method of
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Detection
Malfunction
Error is generated under no common power supply when the power is on.
Decision
Conditions
" Defect of moving part of electronic expansion valve
Supposed
" Defect of outdoor unit PCB (A1P)
Causes
" Defect of connecting cable
314