SiENBE18-621
5. Other Control
5.1
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting" or
external input by external control adapter is required.
[Demand 1 setting]
Demand 1 setting 1
Demand 1 setting 2 (factory setting)
Demand 1 setting 3
5.2
Heating Operation Prohibition
Heating operation is prohibited above 24°CDB outdoor air temperature.
Function
Setting
Standard for upper limit of power consumption
Approx. 60%
Approx. 70%
Approx. 80%
Other Control
79