Shutter Drive Motor / Shutter Limit Switch Abnormality - Daikin E-Series Service Manual

Hide thumbs Also See for E-Series:
Table of Contents

Advertisement

SiENBE18-621
4.5

Shutter Drive Motor / Shutter Limit Switch Abnormality

C7
Remote Control
Display
Method of
The shutter open / close performance is detected by the limit switch attached on its structure. In
this way, the shutter drive motor and the shutter limit switch are checked for failure.
Malfunction
Detection
Malfunction
When the shutter is open, the limit switch is closed.
Decision
Conditions
" Shutter drive motor defective
Supposed
" Shutter limit switch defective
Causes
" Shutter itself deformed (warped)
" Shutter's sealing material too thick
" Detection error by broken relay harness or disconnected connector
" Detection error due to defective PCB (2)
" Foreign substance in blow port
Troubleshooting
Check No.03
Refer to P.278
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn off the power.
Foreign substance in
the shutter
structure?
NO
Check No. 03
Check the limit switch continuity.
Limit switch on power?
YES
Open the shutter and turn on the
power.
Shutter closed?
YES
Shutter opening itself?
NO
YES
NO
Relay harness
NO
broken or connector
disconnected?
NO
YES
Troubleshooting for RA Indoor Unit
Remove such substance.
Replace the limit switch.
YES
Reconnect the connector or
replace the relay harness.
Replace the shutter drive
motor or the PCB (2).
Check the shutter's sealing
material.
Check the shutter for
deformation or its sealing
material.
(Q0410)
277