Procedure of Self-Diagnosis by Remote Controller

4.

Procedure of Self-Diagnosis by Remote Controller

4.1

The INSPECTION/TEST Button

Explanation
By turning the remote controller's inspection /test button ON, you can change the mode as shown in the
figure on the right.
„ When in the inspection mode, malfunction contents can be cleared by continuing to press the ON/OFF
„ To carry out a test run, follow the procedure below.
1. Open the gas side stop valve all the way
2. Open the liquid side stop valve all the way.
3. Energize the crank case heater for 6 hours.
4. Enter the test run mode.
5. Continue to operate by the operation switch for 3 minutes.
6. Enter the normal mode.
7. Check the functions according to the operation manual.
92
button for 5 seconds.
(Let you know completion timing by blinking.)
Si-71A
Troubleshooting