[2-4 M-NET Address Settings ]
2-4-5
Start/Stop Control of Indoor Units
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by the
*1,*2,*3
plug
Automatic restoration
after power failure
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
belt heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
2-4-6
Miscellaneous Settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.")
When using indoor unit as a cooling-only unit, set SW3-1 to ON.
HWE13080
Operation of the indoor unit when the operation is resumed after the unit
Indoor unit will go into operation regardless of its operation status before
power off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before
power off (power failure).
was stopped
- 25 -
*4 *5
Setting (SW1)
9
10
OFF
ON
ON
OFF
OFF
OFF
GB
Need help?
Do you have a question about the PURY-HP72 and is the answer not in the manual?
Questions and answers
what is the set up mode for recovery, and charging of sys?
Why can control my indoor unit with centralize control
You may not be able to control your Mitsubishi Electric PURY-HP72 indoor unit with centralized control for the following reasons:
1. The power jumper connector on the outdoor unit may not be correctly set. It should be connected to CN40 on only one outdoor unit.
2. The central control switch (SW5-1) on the control board of all outdoor units must be set to "ON."
3. Address settings may not be correctly configured. The main indoor unit should be assigned the smallest address (e.g., IC00), and correct port number settings are required.
4. If using a remote controller alone, an interlock setting from the remote controller is needed.
5. Both ME and MA remote controllers cannot be connected to the same indoor unit group.
6. System controller power issues may occur if the outdoor unit fan rotates due to external forces, causing the system controller to detect an error.
7. Improper wiring or incorrect voltage at TB7 may also prevent operation.
Check each of these conditions to ensure proper centralized control.
This answer is automatically generated
Why can’t control indoor unit with centralize control and stay the MA control set up can’t. Control the mode
The Mitsubishi Electric PURY-HP72 indoor unit cannot be controlled with centralized control and the mode control setup does not function due to the following reasons:
1. Central control is not possible if the indoor/outdoor transmission line is used, even if TB7 terminals are daisy-chained.
2. Shielded cables must be used, and the connection must only be made after confirming the voltage is below 20 VDC.
3. Improper connection of the transmission line for centralized control, such as not correctly daisy-chaining terminals M1 and M2 or not short-circuiting the earth and S terminals on TB7.
4. If a power supply unit is not connected to the centralized control line, the power jumper connector must be moved from CN41 to CN40 on one outdoor unit—if this is not done, mode control will not function.
5. Overlapped indoor unit addresses or noise interference on the remote controller lines can also prevent proper control.
6. Failure to set one MA remote controller to MAIN or exceeding its capacity can result in control failure.
All these factors must be correctly configured for centralized and mode control to function properly.
This answer is automatically generated