Units In The Heating Mode Do Not Operate At Expected Capacity - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[8-3 Refrigerant Control Problems ]
8-3-2

Units in the Heating Mode Do Not Operate at Expected Capacity.

1. Phenomena
Although heating operation starts with the normal remote controller display, the capacity is not enough.
2. Cause, check method and remedy
1.
Compressor frequency does not rise sufficiently.
Faulty detection of pressure sensor.
Protection works and compressor frequency does
not rise due to high discharge temperature
Protection works and compressor frequency does
not rise due to high pressure.
HWE13080
Cause
- 261 -
Check method and remedy
(1)
Check pressure difference between the detected
pressure by the pressure sensor and the actual
pressure with self-diagnosis LED.
→ If the accurate pressure is not detected, check
the pressure sensor. Refer to the following page(s).
[8-5-1 Comparing the High-Pressure Sensor Mea-
surement and Gauge Pressure](page 267)
Note:
Higher inlet pressure by the high pressure sensor
than the actual pressure causes insufficient capac-
ity.
SW4 setting (SW6-10: OFF)
High pressure sensor
SW4
ON
Low pressure sensor
SW4
ON
For how to read the SW settings, refer to the fol-
lowing page(s). [9-1-1 How to Read the
LED](page 325)
(2)
Check the difference between the condensing tem-
perature (Tc) and the target condensing tempera-
ture (Tcm) with self-diagnosis LED.
Note:
Higher Tc than Tcm causes insufficient capacity.
SW4 setting (SW6-10: OFF)
Condensing temperature Tc
ON
Target condensing temperature Tcm
ON
For how to read the SW settings, refer to the fol-
lowing page(s). [9-1-1 How to Read the
LED](page 325)
Note:
Protection works and compressor frequency does
not rise even at lower Tc than Tcm due to high dis-
charge temperature and high pressure.
At high discharge temperature:
Refer to the following page(s).[7-3-1 Error Code
[1102]](page 180)
At high pressure:
Refer to the following page(s).[7-3-3 Error Code
[1302] (during operation)](page 182)
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
SW4
1 2 3 4 5 6 7 8 9 10
SW4
1 2 3 4 5 6 7 8 9 10
GB

Hide quick links: