Refrigerant Charging - Mitsubishi Electric PURY-HP72 Service Handbook

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[1-3 Working with Refrigerant Piping ]
1-3-4

Refrigerant Charging

Cylinder with a siphon
Cylin-
der
Cylinder color R410A is pink.
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled
the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid
phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and be-
come unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check
the type of the cylinder on the label before use.
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in
the liquid state.)
Refer to the following page(s).[8-14 Measures for Refrigerant Leakage](page 311)
HWE13080
Valve
liquid
- 14 -
Cylinder without a siphon
Cylin-
der
Refrigerant charging in the liquid state
Valve
liquid
GB

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PURY-HP72 and is the answer not in the manual?

Questions and answers

roque
March 14, 2025

what is the set up mode for recovery, and charging of sys?

Ariel Lituma
April 15, 2025

Why can control my indoor unit with centralize control

1 comments:
Mr. Anderson
April 15, 2025

You may not be able to control your Mitsubishi Electric PURY-HP72 indoor unit with centralized control for the following reasons:

1. The power jumper connector on the outdoor unit may not be correctly set. It should be connected to CN40 on only one outdoor unit.

2. The central control switch (SW5-1) on the control board of all outdoor units must be set to "ON."

3. Address settings may not be correctly configured. The main indoor unit should be assigned the smallest address (e.g., IC00), and correct port number settings are required.

4. If using a remote controller alone, an interlock setting from the remote controller is needed.

5. Both ME and MA remote controllers cannot be connected to the same indoor unit group.

6. System controller power issues may occur if the outdoor unit fan rotates due to external forces, causing the system controller to detect an error.

7. Improper wiring or incorrect voltage at TB7 may also prevent operation.

Check each of these conditions to ensure proper centralized control.

This answer is automatically generated

Ariel Lituma
April 15, 2025

Why can’t control indoor unit with centralize control and stay the MA control set up can’t. Control the mode

1 comments:
Mr. Anderson
April 15, 2025

The Mitsubishi Electric PURY-HP72 indoor unit cannot be controlled with centralized control and the mode control setup does not function due to the following reasons:

1. Central control is not possible if the indoor/outdoor transmission line is used, even if TB7 terminals are daisy-chained.
2. Shielded cables must be used, and the connection must only be made after confirming the voltage is below 20 VDC.
3. Improper connection of the transmission line for centralized control, such as not correctly daisy-chaining terminals M1 and M2 or not short-circuiting the earth and S terminals on TB7.
4. If a power supply unit is not connected to the centralized control line, the power jumper connector must be moved from CN41 to CN40 on one outdoor unit—if this is not done, mode control will not function.
5. Overlapped indoor unit addresses or noise interference on the remote controller lines can also prevent proper control.
6. Failure to set one MA remote controller to MAIN or exceeding its capacity can result in control failure.

All these factors must be correctly configured for centralized and mode control to function properly.

This answer is automatically generated

Table of Contents

Save PDF