[7-4 Error Code Definitions and Solutions: Codes [2000 - 2999] ]
7-4-2

Error Code [2500] (Models with a float switch)

1. Error code definition
Drain sensor submergence
2. Error definition and error detection method
1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and
when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage. While this error is being
detected, humidifier output cannot be turned on.
2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is
detected two consecutive times, water leakage error water leakage is detected, and "2500" appears on the monitor.
3) Detection of water leakage is also performed while the unit is stopped.
4) Preliminary water leakage is cancelled when the following conditions are met:
One hour after the preliminary water leakage was detected, it is not detected that the drain pump goes from OFF to ON.
The operation mode is changed to Cool/Dry.
The liquid pipe temperature minus the inlet temperature is - 10°C [ -18°F] or less.
3. Cause, check method and remedy
(1)
Drain water drainage problem
Clogged drain pump
Clogged drain piping
Backflow of drain water from other units
(2)
Stuck float switch
Check for slime in the moving parts of the float
switch.
(3)
Float switch failure
<Reference>
Drain pump operation triggered by a submergence of the liquid level sensor
(except during the Cooing/Dry mode)
Drain pump
output
Float switch
input
HWE13080
Cause
6 minutes
ON
OFF
ON
OFF
15
15
seconds
seconds
Submergence of
Sensor in the air
the sensor
Preliminary water leakage
Within 1-hour period
- 185 -
Check method and remedy
Check for proper drainage.
Check for normal operation of the float switch.
Check the resistance with the float switch turned on and
turned off.
6 minutes
15
15
15
seconds
seconds
seconds
Submergence of
Submergence of
Sensor in the air
the sensor
the sensor
Water leakage
Within 1-hour period
GB