[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
7-8-11
Error Code [6607] Error Source Address = LOSSNAY (LC)
1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
Error display
ME remote controller (RC), MA remote controller (MA)
Types of refrigerant systems
Single refrigerant system
Troubleshooting problems for
LOSSNAY units
(1) Troubleshooting problems for LOSSNAY units
(1)
Incidental cause
(2)
The power source of LOSSNAY has been shut off.
(3)
When the address of LOSSNAY is changed in the middle
of the operation
(4)
Faulty or disconnected transmission wiring of LOSSNAY
(5)
Disconnected connector (CN1) on LOSSNAY
(6)
Controller failure of LOSSNAY
HWE13080
Grouped operation of multiple
refrigerant systems
Troubleshooting problems for
LOSSNAY units
&
Troubleshooting problems for
all units (A)
Cause
- 229 -
Check method and remedy
1)
Turn off the power source of LOSSNAY and turn it
on again.
2)
If the error is accidental, it will run normally.
If not, check the causes (2) - (6).
GB
Need help?
Do you have a question about the PURY-HP72 and is the answer not in the manual?
Questions and answers
what is the set up mode for recovery, and charging of sys?
Why can control my indoor unit with centralize control
You may not be able to control your Mitsubishi Electric PURY-HP72 indoor unit with centralized control for the following reasons:
1. The power jumper connector on the outdoor unit may not be correctly set. It should be connected to CN40 on only one outdoor unit.
2. The central control switch (SW5-1) on the control board of all outdoor units must be set to "ON."
3. Address settings may not be correctly configured. The main indoor unit should be assigned the smallest address (e.g., IC00), and correct port number settings are required.
4. If using a remote controller alone, an interlock setting from the remote controller is needed.
5. Both ME and MA remote controllers cannot be connected to the same indoor unit group.
6. System controller power issues may occur if the outdoor unit fan rotates due to external forces, causing the system controller to detect an error.
7. Improper wiring or incorrect voltage at TB7 may also prevent operation.
Check each of these conditions to ensure proper centralized control.
This answer is automatically generated
Why can’t control indoor unit with centralize control and stay the MA control set up can’t. Control the mode
The Mitsubishi Electric PURY-HP72 indoor unit cannot be controlled with centralized control and the mode control setup does not function due to the following reasons:
1. Central control is not possible if the indoor/outdoor transmission line is used, even if TB7 terminals are daisy-chained.
2. Shielded cables must be used, and the connection must only be made after confirming the voltage is below 20 VDC.
3. Improper connection of the transmission line for centralized control, such as not correctly daisy-chaining terminals M1 and M2 or not short-circuiting the earth and S terminals on TB7.
4. If a power supply unit is not connected to the centralized control line, the power jumper connector must be moved from CN41 to CN40 on one outdoor unit—if this is not done, mode control will not function.
5. Overlapped indoor unit addresses or noise interference on the remote controller lines can also prevent proper control.
6. Failure to set one MA remote controller to MAIN or exceeding its capacity can result in control failure.
All these factors must be correctly configured for centralized and mode control to function properly.
This answer is automatically generated