Mitsubishi Electric PURY-HP72 Service Handbook page 273

R410a
Hide thumbs Also See for PURY-HP72:
Table of Contents

Advertisement

[8-3 Refrigerant Control Problems ]
2.
Indoor unit LEV malfunction
Insufficient refrigerant flows due to LEV malfunction
(not enough opening).
3.
Temperature reading error on the indoor unit piping
temperature sensor
If the temperature reading on the sensor is higher
than the actual temperature, it makes the subcool
seem smaller than it is, and the LEV opening de-
creases too much.
4
RPM error of the outdoor unit FAN
Motor failure or board failure, or airflow rate de-
crease, pressure drop due to clogging of the heat
exchanger leading to high discharge temperature
The fan is not properly controlled as the tempera-
ture cannot be precisely detected with the piping
sensor.
5.
Insulation failure of the refrigerant piping
6.
Long piping length
Excessively long piping on the high pressure side
causes pressure loss leading to increase in the high
pressure.
7.
Piping size is not proper (thin)
8.
Clogging by foreign object
9.
The indoor unit inlet temperature is excessively
high.(exceeding 28°C [82°F])
10.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to low discharge temperature
Refrigerant recovery operation is likely to start.
11.
Compressor failure (same as in case of cooling)
12.
BC controller LEV 3 actuation failure
A drop in the low pressure that is caused either by a
blockage of liquid pipe or by a pressure loss and the
resultant slowing of refrigerant flow causes a tenden-
cy for the discharge temperature to rise.
HWE13080
Cause
Check method and remedy
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems](page 273)
Check the thermistor.
Refer to the following page(s).
[8-7 Troubleshooting Outdoor Unit Fan Prob-
lems](page 272)
Confirm that the characteristic of capacity drop due
to piping length.
→ Change the pipe
Check the temperature difference between the up-
stream and the downstream of the pipe section that
is blocked. Since blockage in the extended section
is difficult to locate, operate the unit in the cooling
cycle, and follow the same procedures that are
used to locate the blockage of pipe during cooling
operation.
→ Remove the blockage in the pipe.
Check the inlet air temperature and for short cy-
cling. Change the environment where the indoor
unit is used.
Refer to item 1 (Compressor frequency does not
rise sufficiently.) on the previous page. (page 261)
Refer to the following page(s).[6-9 Evaluating and
Adjusting Refrigerant Charge](page 161)
Check the discharge temperature.
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems](page 273)
- 262 -
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents