6. Heating [All indoor units]
6-6. Heating capacity with PUHY-P300YRJC-A "COP priority mode"
All Indoor units
Model
Outdoor
size
air temp.
15°C D.B.
(Rated kW)
°C W.B.
SHC
-20.0
1.0
-15.0
1.2
-10.0
1.4
-5.0
1.6
0.0
1.8
15
2.5
1.9
(1.9)
6.0
2.0
7.5
2.0
10.0
2.2
12.5
2.3
15.5
2.4
-20.0
1.3
-15.0
1.6
-10.0
1.8
-5.0
2.1
0.0
2.4
20
2.5
2.5
(2.5)
6.0
2.6
7.5
2.7
10.0
2.8
12.5
3.0
15.5
3.2
-20.0
1.4
-15.0
1.7
-10.0
2.0
-5.0
2.3
0.0
2.6
22
2.5
2.8
(2.8)
6.0
2.9
7.5
3.0
10.0
3.2
12.5
3.4
15.5
3.6
-20.0
1.6
-15.0
2.0
-10.0
2.3
-5.0
2.7
0.0
3.0
25
2.5
3.2
(3.2)
6.0
3.3
7.5
3.4
10.0
3.6
12.5
3.9
15.5
4.1
-20.0
1.8
-15.0
2.2
-10.0
2.6
-5.0
3.0
0.0
3.4
28
2.5
3.6
(3.6)
6.0
3.7
7.5
3.9
10.0
4.1
12.5
4.3
15.5
4.6
-20.0
2.0
-15.0
2.5
-10.0
2.9
-5.0
3.3
0.0
3.8
32
2.5
4.0
(4.0)
6.0
4.1
7.5
4.3
10.0
4.6
12.5
4.8
15.5
5.1
-20.0
2.3
-15.0
2.8
-10.0
3.3
-5.0
3.8
0.0
4.3
36
2.5
4.5
(4.5)
6.0
4.7
7.5
4.8
10.0
5.1
12.5
5.4
15.5
5.8
SHC:Sensible Heat Capacity(kW)
Indoor air temp.
20°C D.B.
25°C D.B.
27°C D.B.
SHC
SHC
SHC
1.0
1.0
0.9
1.2
1.1
1.1
1.4
1.3
1.3
1.6
1.5
1.3
1.8
1.5
1.3
1.9
1.5
1.3
1.9
1.5
1.3
1.9
1.5
1.3
1.9
1.5
1.3
1.9
1.5
1.3
1.9
1.5
1.3
1.3
1.3
1.2
1.5
1.5
1.5
1.8
1.7
1.7
2.1
2.0
1.8
2.3
2.0
1.8
2.5
2.0
1.8
2.5
2.0
1.8
2.5
2.0
1.8
2.5
2.0
1.8
2.5
2.0
1.8
2.5
2.0
1.8
1.4
1.4
1.4
1.7
1.7
1.7
2.0
2.0
1.9
2.3
2.2
2.0
2.6
2.2
2.0
2.8
2.2
2.0
2.8
2.2
2.0
2.8
2.2
2.0
2.8
2.2
2.0
2.8
2.2
2.0
2.8
2.2
2.0
1.6
1.6
1.6
2.0
1.9
1.9
2.3
2.2
2.2
2.6
2.6
2.2
3.0
2.6
2.2
3.2
2.6
2.2
3.2
2.6
2.2
3.2
2.6
2.2
3.2
2.6
2.2
3.2
2.6
2.2
3.2
2.6
2.2
1.8
1.8
1.8
2.2
2.2
2.1
2.6
2.5
2.5
3.0
2.9
2.5
3.4
2.9
2.5
3.6
2.9
2.5
3.6
2.9
2.5
3.6
2.9
2.5
3.6
2.9
2.5
3.6
2.9
2.5
3.6
2.9
2.5
2.0
2.0
2.0
2.4
2.4
2.4
2.9
2.8
2.7
3.3
3.2
2.8
3.7
3.2
2.8
4.0
3.2
2.8
4.0
3.2
2.8
4.0
3.2
2.8
4.0
3.2
2.8
4.0
3.2
2.8
4.0
3.2
2.8
2.3
2.3
2.2
2.7
2.7
2.7
3.2
3.1
3.1
3.7
3.6
3.2
4.2
3.6
3.2
4.5
3.6
3.2
4.5
3.6
3.2
4.5
3.6
3.2
4.5
3.6
3.2
4.5
3.6
3.2
4.5
3.6
3.2
kcal/h=kW x 860 , BTU/h = kW x 3,412
INDOOR UNITS
All Indoor units
Model
Outdoor
size
air temp.
15°C D.B.
(Rated kW)
°C W.B.
SHC
-20.0
2.6
-15.0
3.1
-10.0
3.6
-5.0
4.2
0.0
4.7
40
2.5
5.0
(5.0)
6.0
5.2
7.5
5.4
10.0
5.7
12.5
6.0
15.5
6.4
-20.0
2.9
-15.0
3.5
-10.0
4.1
-5.0
4.7
0.0
5.3
45
2.5
5.6
(5.6)
6.0
5.8
7.5
6.0
10.0
6.4
12.5
6.7
15.5
7.2
-20.0
3.2
-15.0
3.9
-10.0
4.6
-5.0
5.3
0.0
6.0
50
2.5
6.3
(6.3)
6.0
6.5
7.5
6.8
10.0
7.2
12.5
7.6
15.5
8.1
-20.0
3.6
-15.0
4.3
-10.0
5.1
-5.0
5.9
0.0
6.6
56
2.5
7.0
(7.0)
6.0
7.3
7.5
7.5
10.0
8.0
12.5
8.4
15.5
9.0
-20.0
4.1
-15.0
5.0
-10.0
5.8
-5.0
6.7
0.0
7.6
63
2.5
8.0
(8.0)
6.0
8.3
7.5
8.6
10.0
9.1
12.5
9.6
15.5
10.3
-20.0
4.6
-15.0
5.6
-10.0
6.6
-5.0
7.5
0.0
8.5
71
2.5
9.0
(9.0)
6.0
9.3
7.5
9.7
10.0
10.3
12.5
10.8
15.5
11.5
-20.0
5.1
-15.0
6.2
-10.0
7.3
-5.0
8.4
0.0
9.5
80
2.5
10.0
(10.0)
6.0
10.4
7.5
10.7
10.0
11.4
12.5
12.0
15.5
12.8
C7-R Rev.
SHC:Sensible Heat Capacity(kW)
Indoor air temp.
20°C D.B.
25°C D.B.
27°C D.B.
SHC
SHC
SHC
2.5
2.5
2.5
3.1
3.0
3.0
3.6
3.5
3.4
4.1
4.0
3.5
4.7
4.0
3.5
4.9
4.0
3.5
5.0
4.0
3.5
5.0
4.0
3.5
5.0
4.0
3.5
5.0
4.0
3.5
5.0
4.0
3.5
2.8
2.8
2.8
3.4
3.4
3.3
4.0
3.9
3.8
4.6
4.5
3.9
5.2
4.5
3.9
5.5
4.5
3.9
5.6
4.5
3.9
5.6
4.5
3.9
5.6
4.5
3.9
5.6
4.5
3.9
5.6
4.5
3.9
3.2
3.2
3.1
3.8
3.8
3.7
4.5
4.4
4.3
5.2
5.0
4.4
5.9
5.0
4.4
6.2
5.0
4.4
6.3
5.0
4.4
6.3
5.0
4.4
6.3
5.0
4.4
6.3
5.0
4.4
6.3
5.0
4.4
3.5
3.5
3.5
4.3
4.2
4.1
5.0
4.9
4.8
5.8
5.6
4.9
6.5
5.6
4.9
6.9
5.6
4.9
7.0
5.6
4.9
7.0
5.6
4.9
7.0
5.6
4.9
7.0
5.6
4.9
7.0
5.6
4.9
4.0
4.0
4.0
4.9
4.8
4.7
5.7
5.6
5.5
6.6
6.4
5.6
7.5
6.4
5.6
7.9
6.4
5.6
8.0
6.4
5.6
8.0
6.4
5.6
8.0
6.4
5.6
8.0
6.4
5.6
8.0
6.4
5.6
4.5
4.5
4.5
5.5
5.4
5.3
6.5
6.3
6.2
7.4
7.2
6.3
8.4
7.2
6.3
8.9
7.2
6.3
9.0
7.2
6.3
9.0
7.2
6.3
9.0
7.2
6.3
9.0
7.2
6.3
9.0
7.2
6.3
5.0
5.0
5.0
6.1
6.0
5.9
7.2
7.0
6.8
8.3
8.0
7.0
9.4
8.0
7.0
9.9
8.0
7.0
10.0
8.0
7.0
10.0
8.0
7.0
10.0
8.0
7.0
10.0
8.0
7.0
10.0
8.0
7.0
kcal/h=kW x 860 , BTU/h = kW x 3,412