Position and Level the Tumble Dryer

The tumble dryer may be moved with or without the
skid. To remove the skid, unscrew the four shipping
bolts, and discard them.
To fit a 170 and 200 series tumble dryer (with shipping
skid) through a 2.43 meters (8 foot) high door, you
must remove the front access panel. The upper 76 mm
(3 inches) of the stove must also be removed on
170 series gas tumble dryers. Removing the entire gas
or steam heater assembly and the shipping skid, will
reduce the height of the 120 series tumble dryer to
1778 mm (70 inches), and the 170 and 200 series
tumble dryer to 1905 mm (75 inches).
Level the tumble dryer to within 3 mm (0.125 inch)
from front-to-rear (level on cylinder rib), and side-to-
side (level on top panel). Shim under corners to level
and stabilize unit. Tumble dryer must not rock.
70458101 (EN)
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

Fire Suppression System

Check Local Codes and Permits

Call your local water company or the proper municipal
authority for information regarding local codes.
IMPORTANT: It is your responsibility to have
ALL plumbing connections made by a qualified
professional to assure that the plumbing is
adequate and conforms to local, state, and federal
regulations or codes.
IMPORTANT: It is the installation or owner's
responsibility to see that the necessary or required
water, water pressure, pipe size, or connections are
provided. Manufacturer assumes no responsibility
if the fire suppression system is not connected,
installed, or maintained properly.

Water Requirements

IMPORTANT: Water must be supplied to the fire
suppression system, or the fire suppression system
will not operate as intended.
Connection point to the electric water solenoid valve is
a 19 mm (3/4 inch) hose. The fire suppression system
equipped tumble dryer must be supplied with a
minimum water pipe size of 12.7 mm (1/2 inch) and be
provided with a minimum of 138 kPa (20 psi) and a
maximum of 827 kPa (120 psi) of pressure at all times.
Flow rate must be no less than, but approximately
57 liters (15 gallons) per minute.
NOTE: Water pressure under 138 kPa (20 psi) will
cause low flow and water leakage at water solenoid
valve.
If the rear of the tumble dryer or the water supply is
located in an area where it will be exposed to cold/
freezing temperatures, provisions must be made to
protect these water lines from freezing.
IMPORTANT: Temperature of the water supply
must be kept between 4.4°C and 48.9°C (40°F and
120°F). If water in the supply line or water solenoid
valve freezes, the fire suppression system will not
operate.