Configuration
Wired Communication Parameters - Serial Interface
Parameter
Termination
Resistor
Selection
Termination
Resistor
Protocol
Selection
Table 5.7Wired Communication Parameters - Serial Interface
5.5.2
Interfaces > Ethernet
The Gateway can connect to the host system via an Ethernet interface or a Serial interface.
The parameters concerning the Ethernet interface can be found here.
Figure 5.6Parameter > Wired Communication > Interfaces > Ethernet
Caution!
Possible loss of Ethernet connection
After enabling DHCP using the IP address assignment (DHCP) parameter, the host could
loose the Ethernet connection due to the new, automatically assigned IP address.
Description
Select if you prefer to activate the Gateway's
termination resistor via the DIP switches inside the
Gateway housing (see chapter 6.1) or under
software control.
Connect or disconnect the Gateway's termination
resistor. This drop-down list depends on the value of
Termination Resistor Selection. If the value of
Termination Resistor Selection is "DIP switches",
this checkbox is read only.
Select the protocol you prefer to use for serial
communication – HART or Modbus RTU.
Default
DIP switches
disconnected
HART