Pepperl+Fuchs WHA-GW Manual page 73

Wirelesshart gateway
Table of Contents

Advertisement

WHA-GW-*
Operation
Parameter
Ethernet Communication
Fault
Electronic Defect
RS-485 Communication
Fault
Gateway Operation in Progress
Block transfer
Delayed answer
Self-test
File update
Start-up phase
Extended List Changes
Instrument List changed
Active Device List changed
Cumulative Device Status
These bits are set to 1 whenever the related status applies to one or more devices (or
sub-devices) connected to the gateway.
Primary Variable out of
Limits
Non-Primary Variable out of
Limits
Loop Current Saturated
Loop Current Fixed
More status available
Cold Start
Description
Non-recoverable hardware fault within the communication
controller associated with the Ethernet interface.
Non-recoverable hardware fault within the Gateway
different from the other faults in the "Extended Device
Malfunction" category.
Non-recoverable hardware fault within the communication
controller associated with the RS-485 interface.
When the checkbox is activated, this shows that block-
transfer activity is going on in the Gateway.
When the checkbox is activated, this shows that delayed-
answer activity is going on in the Gateway, which can be
related either to a Gateway buffer or to a connected
device's buffer.
This bit is associated with a self-test activity triggered by
CMD 41. The checkbox remains activated until the activity
has been completed.
If required, the Gateway can write persistent (i.e. non-
volatile) information to its local file system. The checkbox
remains activated as long as information is being written to
the file system.
At each power-up or software restart / reset (triggered by
CMD 42 & 141), the Gateway polls all devices within the
Instrument List to check their communication statuses and
to update their identity information. The checkbox remains
activated until the start-up phase has been completed.
This checkbox is activated whenever the Instrument List
content is changing.
This checkbox is activated whenever the "Active Device
list" content is changing. This is the case when a
"communication loss" or a "communication recovered"
event takes place for a device.
The PV is beyond its operating limits.
A device variable not mapped to the PV is beyond its
operating limits.
The loop current has reached its upper (or lower) endpoint
limit and cannot increase (or decrease) any further.
The loop current is being held at a fixed value and is not
responding to process variations.
More status information is available via Command 48
(Read Additional Status Information).
A power failure or device reset has occurred.
73