Soft Keys, continued:
Setup –
Configures the inverter/charg er. Options include:
•
Search
Used to set the search watts at which the inverter will come out of "sleep"
mode. Selections are 3-75 watts.
•
LBCO (Low Battery Cut Out)
Used to set the DC voltage level to shut down the inverter and protect the
batteries from over-discharge damage. Selections are 9.0 VDC, 10.0
VDC and 11.0 VDC. DC volts must reach and maintain LBCO
setting for 1 minute before inverter shut down is initiated.
•
Battery Size
Used to select the approximate battery bank capacity. Selections are in 200
amp increments from 200 -1000 amps. Battery capacity is also used to
determine absorption time during battery charging. See Chart 2.
•
Battery Charge Rate
Used to set the maximum charge rate during bulk, absorption or float
charge. Selections are in 10 amp increments from 10% - 100%.
•
Battery Type
Used to select battery type for the battery charge profile. Selections are
Gel, AGM (Absorbed Glass Mat), Liquid Lead Acid (Flooded) and
Custom (future). See Chart 1.
•
C o n t r a s t
U s e d t o a d j u s t t h e L C D c o n t r a s t .
•
AC Dropout Voltage
Used to select the AC voltage threshold (60, 90, 100 VAC) where the
inverter transfers from AC line to inverter mode.
•
Tech – (display only)
Reserved for future, this feature is used for troubleshooting the
inverter/charger. Options in clude FET temp, transformer temp, and
battery temp.
Factory Reset
Restores all settings to factory defaults. press and hold the switch the switch
for 5 seconds. "Reset Complete" will be appear in the display. See Chart 3.