1.1 TOP COVER REMOVAL
2.1.a Top cover is attached with 6 - #10 x 5/8 Torx screws (#25 bit) and 1- #6 x 1/2
Torx screw (#15 bit). Remove all seven screws and pull straight up to remove top cover.
2.2.a
Remove top cover per 2.1
2.2.b
Remove 4- #6 x ½ Torx screws from corners of ac board
2.2.c
Use a utility knife or sharp chisel to cut temp sensor loose then
clean remaining silicon from transformer.
2.2.d Mark and remove ac wires from ac board being careful to note
the
orientation of the
wire from the transformer location. Also note the
start
black
and
orange
wire. Miswiring of these