To Verify The Operation Of The Slide Rails And Cma; Figure 2-7 Installing Cma Cable Hangers - Sun Microsystems Sun Fire V210 Installation Manual

Hide thumbs Also See for Sun Fire V210:
Table of Contents

Advertisement

6. Position the cable hangers in the appropriate mounting holes in the CMA and
snap them into place (
Installing CMA Cable Hangers
FIGURE 2-7
7. Install the cables to the server, as required.
Refer to the Sun Fire V210 and V240 Servers Getting Started Guide for information
about the locations of the power inlets and I/O ports on the front and back of the
servers.
8. Route the cables through the CMA cable hangers.
To Verify the Operation of the slide rails and
CMA
Note – Two people are recommended for this procedure: one to move the server in
and out of the rack and one to observe the cables and CMA.
1. Slowly pull the server out of the rack until the slide rails reach their stops.
2. Inspect the attached cables for any binding or kinks.
3. Verify that the CMA extends fully and does not bind in the slide rails.
4. Push the server back into the rack, as described below.
When the server is fully extended, you must release two sets of slide rail stops to
return the server to the rack:
).
FIGURE 2-7
Chapter 2 Installing the Hardware
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun fire v240

Table of Contents