3.3.4 Combined operation mode 1 (Operation using both external
start signal and control panel)
When the start signal is provided externally (switch etc.) and the running frequency is
set from the control panel (Pr. 79 = 3).
The external frequency setting signal and PU's forward rotation, reverse rotation and
STOP
keys are not accepted. (Note)
RESET
Operation command: externally connected start signal
Frequency setting:
Step
Power on
Switch power on.
1
Operation mode selection
Refer to page 55 and set "3" in Pr. 79 "operation mode
selection".
2
Start
Turn on the start switch (STF or STR).
Note: The motor does not start if both the forward and
reverse rotation switches are turned on. If both
3
switches are turned on during operation, the motor
decelerates to a stop.
The [RUN] indication is lit to indicate forward
rotation, or flickers to indicate reverse rotation.
Running frequency setting
Set the running frequency to 60.00Hz with the
key.
4
Stop
Turn off the start switch (STF or STR).
The motor stops.
5
The [RUN] indication goes off.
STOP
Note: The
key is made valid if any of "14" to "17" is set in Pr. 75 "PU stop
RESET
selection".
/
key of the control panel (FR-PA02
Description
62
)
-02
Image
ON
Flicker
Forward rotation
Reverse
rotation
ON
/
<Step setting>
Hz
RUN
MON
PU
EXT
3
Hz
MON
PU
EXT