Pr. 903 "frequency setting voltage gain"
(Pr.902, Pr. 904, Pr. 905 can also be adjusted similarly.)
<Adjustment procedure>
(1)Power-on (monitoring mode)
(2)Choose the PU operation mode.
1) Using the
MODE
z
Monitoring mode
Hz
MON
PU
EXT
When using an external frequency setting signal to set the
frequency.
MODE
SET
STOP
FWD
RESET
key, make sure that the PU operation mode has been selected.
z
Frequency setting
mode
MODE
z
Help mode
MODE
Hz RUN
A
MON
PU
EXT
REV
z
Parameter setting
mode
MODE
Hz
PU
z
Operation mode
(PU operation mode)
MODE
PU EXT
MODE
SET
FWD
Confirm that the PU operation mode
(
) has been chosen.
In the JOG operation mode (
or external operation mode (
press the
/
If
cannot be displayed by pressing
the
/
key in the external operation mode
(
).
(if Pr. 79 "operation mode selection" ≠ "0"),
refer to 2) and set "1" (PU operation mode)
in Pr. 79 "operation mode selection".
158
PARAMETERS
MODE
PU
PU
REV
STOP
RESET
)
),
key to display
.