Download  Print this page

Starting Frequency (pr. 13) - Mitsubishi Electric FR-E500 Instruction Manual

Fr-e500 series transistorized inverter.
Hide thumbs

Advertisement

4.2.8 Starting frequency (Pr. 13)

Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
y Set the starting frequency at which the start signal is switched on.
Parameter
Factory
Number
Setting
13
0.5Hz
Note: The inverter will not start if the frequency setting signal is less than the value
set in Pr. 13 "starting frequency".
For example, when 5Hz is set in Pr. 13, the motor will not start running until
the frequency setting signal reaches 5Hz.
When the Pr. 13 setting is lower than the Pr. 2 value, note that the motor
will run at the set frequency by merely switching the start signal on,
without entering the command frequency.
Setting
Output frequency
Range
0.01 to 60Hz
Foward rotation
CAUTION
81
PARAMETERS
Related parameters
Pr. 2 "minimum frequency"
(Hz)
60
Pr.13
0
Frequency setting signal (V)
ON
Time
4

Advertisement

Table of Contents

   Related Manuals for Mitsubishi Electric FR-E500

   Related Content for Mitsubishi Electric FR-E500

This manual is also suitable for:

Fr-e520Fr-e540Fr-e510w

Comments to this Manuals

Symbols: 0
Latest comments: