Mitsubishi Electric FR-E500 Instruction Manual page 161

Fr-e500 series transistorized inverter
Hide thumbs Also See for FR-E500:
Table of Contents

Advertisement

<Setting>
Refer to the following list and set the parameters.
Signal
Setting
Name
0
RL
1
RM
2
RH
3
RT
4
AU
5
STOP
6
MRS
7
OH
8
REX
16
X16
18
X18
**
: When Pr. 59 = "1" or "2", the functions of the RL, RM and RH signals change as
listed above.
**
: Activated when the relay contact "opens".
Note: 1. One function can be assigned to two or more terminals. In this case, the
terminal inputs are OR' ed.
2. The speed command priorities are higher in order of multi-speed setting
(RH, RM, RL, REX) and AU.
3. When V/F control is selected using the V/F-general-purpose magnetic flux
switch-over function, the secondry functions are also selected.
During operation, you cannot switch between V/F and general-purpose
magnetic flux. Should you switch between V/F and general-purpose
magnetic flux, only the second functions are selected.
4. Use common terminals to assign multi-speeds (7 speeds) and remote
setting. They cannot be set individually.
(Common terminals are used since these functions are designed for multiple
speed setting and need not be set at the same time.)
5. Functions are invalid if values other than the above are set to Pr. 180 to
Pr. 183 (input terminal function selection).
Function
Pr. 59 = 0
Low-speed operation command
Pr. 59 = 1, 2 * Remote setting (setting clear)
Middle-speed operation
Pr. 59 = 0
command
Pr. 59 = 1, 2 * Remote setting (deceleration)
Pr. 59 = 0
High-speed operation command
Pr. 59 = 1, 2 * Remote setting (acceleration)
Second function selection
Current input selection
Start self-holding terminal
Output shut-off terminal
External thermal relay input **
The external thermal relay provided for overheat
protection or the embedded temperature relay
within the motor is activated to stop the inverter.
15-speed selection (combination with three speeds
of RL, RM, RH)
PU operation-external operation switch-over
General-purpose magnetic flux vector-V/F switch-
over (OFF: general-purpose magnetic flux vector
control, ON: V/F control) (Note 3)
146
PARAMETERS
Related
Parameters
Pr. 4 to Pr. 6
Pr. 24 to Pr. 27
Pr. 232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6,
Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 4 to Pr. 6,
Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
Pr. 44 to Pr. 48
Refer to page 163.
Pr. 4 to Pr. 6,
Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 79
Pr. 80