Download  Print this page

Mitsubishi Electric FR-E500 Instruction Manual Page 128

Fr-e500 series transistorized inverter.
Hide thumbs

Advertisement

<Operating conditions>
y The motor capacity is equal to or one rank lower than the inverter capacity.
y The number of motor poles is any of 2, 4, and 6. (4 poles only for the constant-
torque motor)
y Single-motor operation (one motor for one inverter) is performed.
y The wiring length between the inverter and motor is within 30m (98.42 feet). (If the
length is over 30m (98.42 feet), perform offline auto tuning with the cables wired.)
<Setting>
( 1 ) General-purpose magnetic flux vector control
y By setting the capacity of the motor used in Pr. 80, you can choose general-purpose
magnetic flux vector control.
Parameter
Setting
Number
0.1 to 7.5/
80
0.2 to 7.5
Note: The setting range changes with the inverter: 0.2kW to 7.5kW, 9999 for the
400V class.
y When using Mitsubishi's constant-torque motor (SF-JRCA), set "1" in Pr. 71. (When
using the SF-JRC, perform the offline auto tuning .)
9999
V/F control
Set the motor capacity applied.
(Note)
Description
113
PARAMETERS
General-
purpose
magnetic flux
vector control
4

Advertisement

Table of Contents

   Related Manuals for Mitsubishi Electric FR-E500

This manual is also suitable for:

Fr-e520Fr-e540Fr-e510w

Comments to this Manuals

Symbols: 0
Latest comments: