Hearth Protection; Clearances; Mantel & Trim; Alcove - Jøtul GF 600 DV II Firelight Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Hearth Requirements
The Firelight gas stove CANNOT be installed direct-
ly on carpeting, vinyl, linoleum or wood laminates,
such as Pergo
.
®
If this appliance is to be installed on any
combustible material OTHER THAN WOOD, a floor
pad must be utilized that is either metal, wood
or a listed hearth pad. This floor protection must
extend the full width and depth of the appliance.
It is not necessary to remove the carpeting, vinyl
or linoleum from underneath the floor protection.
See Fig. 1.
29"
(74 cm)
Figure 1. Minimum Hearth Protection
Stove and Vent Clearance
Requirements
Minimum Clearances:
See figs. 2-3.
Rear:
2" (51 mm)
Ceiling:
30" (762 mm) from Stove Top
Corner:
3" (76 mm) from Stove Top
Sides:
3" (76 mm) from Stove Top
Minimum Clearances from the Vent Pipe
to Combustibles:
Horizontal Run:
Off the top of the pipe -
Off the sides and bottom -
Vertical Run:
All sides
24"
(61 cm)
from Rear Shroud
2" (51 mm)
1" (25 mm)
1" (25 mm)
ALCOVE SPECIFICATIONS:
Maximum Alcove Depth: 24" (61 cm)
Minimum Alcove Width:
Minimum Ceiling Height:
2" (51 mm)
3"
(76 mm)
Figure 2. Parallel Installation Clearances,
measured from Top Plate.
3"
(76 mm)
Figure 3.
Corner Installation Clearance,
measured from Top Plate.
42”
1067 mm
2” (51 mm)
39”
990 mm
36”
40 1/2”
914 mm
1028 mm
37 1/2”
952 mm
31”
787 mm
Figure 4.
Mantel and Trim Clearances: As tested, with back of
stove located 2 in. minimum from fireplace face.
138090_Rev_F
7.29.10
36" (91 cm)
61" (155 cm)
3"
(76 mm)
3"
(76 mm)
Max. Mantel
Depth
11.5”
9.5”
7.5”
5.5”
Min. Mantel
3.5”
Depth
Max. Trim
Depth = 1 1/2”
2” (51 mm)
7