6 Installation
Fig.10
Connecting the condensate dis­
charge pipe
2
1
3
6.4

Gas connection

Fig.11
Connecting the gas pipe
6.5

Air supply/flue gas connections

24
6.3.4
1. Fit a plastic drain pipe of Ø 32 mm or larger, terminating in the drain.
2. Insert the flexible condensate drain hose into the pipe.
3. Fit a stench-trap or siphon in the drain pipe.
Danger
The siphon must always be filled with water. This prevents flue
gases from entering the room.
Caution
4
AD-0000024-02
Warning
1. Remove the dust cap from the gas supply pipe
the boiler.
2. Fit the gas supply pipe.
3. Fit a gas tap in this pipe, directly underneath the boiler.
4. Fit the gas pipe to the gas tap.
Caution
1
2
Important
We recommend installing a gas filter to prevent clogging of the
3
gas valve unit.
4
AD-0000025-02
The boiler is suitable for the following types of flue gas connections:
For more information, see
Certifications, page 12

Connecting the condensate discharge pipe

Never seal the condensate drain.
The drain pipe must slope down at least 30 mm per metre, the
maximum horizontal length is 5 metres.
Condensed water must not be discharged into a gutter.
Before starting work on the gas pipes, turn off the main gas tap.
Before installing, check that the gas meter has sufficient capaci­
ty. Take into account the consumption of all appliances.
Notify the local energy company if the gas meter has insufficient
capacity.
Remove dirt and dust from the gas pipe.
Always perform welding work at a sufficient distance from the
boiler.
at the bottom of
123157 - v.12 - 07022018