6 Installation
Fig.7
Connecting the condensate drain
6.3

Gas connection

Fig.8
Connecting the gas pipe
26
Caution
If using plastic pipes, follow the manufacturer's (connection) in­
structions.
6.2.3

Connecting the condensate discharge pipe

1. Fit a plastic drain pipe of Ø 32 mm or larger to the
drain, terminating in the drain.
Caution
Use only plastic material for the discharge pipe due to the acidi­
ty (pH 2 to 5) of the condensate.
Do not make a fixed connection in order to prevent an overpres­
sure in the siphon.
Never seal the condensate drain.
Condensed water must not be discharged into a gutter.
The drain pipe must slope down at least 5 - 10 mm per metre,
the maximum horizontal length is 5 metres.
AD-4000068-01
1. Before starting work on the gas pipes, turn off the main gas tap.
2. Before installing, check that the gas meter has sufficient capacity.
Take into account the consumption of all appliances.
3. Notify the local energy company if the gas meter has insufficient ca­
pacity.
4. Remove the dust cap on the gas connection .
5. Fit the gas supply pipe.
GAS /
6. Also fit a gas isolation valve in this pipe, near the boiler.
GAZ
Caution
Remove dirt and dust from the gas pipe.
Always perform welding work at a sufficient distance from the
boiler.
Important
AD-4000067-02
We recommend installing a gas filter to prevent clogging of the
gas valve unit.
condensate
114494 - v.05 - 06022018