Addressable fire alarm control panel
Table of Contents

Advertisement

Product Description
The following table shows the ANN-80 connections to the FACP
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must added to the system via FACP programming. Refer to the programming section titled "ANN-
BUS Options" on page 121 in this manual for detailed programming information. Select the LCD
option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.
If the Keyswitch on the ANN-80 is left in the unlocked position for more than 2 minutes, a trouble
condition will be indicated at the FACP.

ANN-S/PG Serial/Parallel Interface Installation

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel
printer to the FACP for a real-time log of system events, detector status reports and event history.
The module is provided with a plastic enclosure for surface mounting. Proceed with the installation
as described in the following:
1.
Ensure that all power (AC and DC) has been removed from the FACP.
2.
Connect the ANN-S/PG to the FACP as illustrated in Figure 1.7.
3.
Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module.
30
FACP
Terminal GND (-) on TB3
Terminal PWR (+)TB3
Terminal ACS on TB6
Terminal ACS on TB6
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
+ - + - + -
TB3
TB4
Figure 1.7 ANN-S/PG Connection to FACP
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
Cable Connectors for
(-)
connection to printer
(+)
A
B
ANN-S/PG Module
TB1
+ -
A B
TB5
TB6
JP8
JP5