Programming
The Canadian Options configures the FACP with the following as required by Canada:

Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the sys-
tem for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all
output devices associated with a waterflow type input device, will be nonsilenceable. When Water-
flow Sil. Yes is selected, all output devices associated with a waterflow type input device, will be
silenceable.
3.6.6 Verify Loops
PROGRAMMING
Pressing 3 while viewing Programming Screen #2, will select the Verify Loops option and display
1=LOOP SETUP
the following screen:
2=SYSTEM SETUP
3=VERIFY LOOPS
Programming Screen #2
During loop verification, the FACP polls each device on the selected SLC to determine if the device
is communicating and whether or not it responds with the proper type identification. The program-
mer can choose to verify one or both loops by pressing the number corresponding to the choices
shown above.
When the selection is made, the following screen will be displayed while verification is in progress:
When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.
114
The following monitor module type codes are not available:
• monitor
• non-latching supervisory
• non-latching drill
• non-latching process monitor
• process monitor
• hazard
• tornado
• medical alert
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.
1=LOOP 1
2=LOOP 2
3=BOTH LOOPS
VERIFYING LOOPS
VERIFY LOOPS
Verify Loop Select Screen
PLEASE WAIT
Verification Progress Screen
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010