The MS-9600LSC is supplied with the DP-9692 Dress Panel.
When installing and programming the FACP, the Canadian Option must be set to ON prior to
any other panel programming (refer to "Canadian Option" on page 113 of the Programming
Section of this manual).
ACS Series annunciators are not compatible for Canadian applications.
The LCD-80FC annunciator can be used for optional ancillary annunciation.
The ANN-LED annunciator must be installed in the same room as the FACP. All wiring
between the FACP and ANN-LED must be in metal conduit no longer than 20 feet.
The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door.
To comply with CAN/ULC - S559-04, the DACT-UD2 and 4XTMF must both be utilized.
Figure G.1 FACP Minimum Configuration - Single ANN-LED Annunciator
Figure G.2 FACP Maximum Configuration - Eight ANN-LED Annunciators
200
metal conduit
(max. 20 ft.)
FACP
metal conduit
(max. 20 ft.)
FACP
ANN-LED annunciator must
be in same room as FACP
ANN-LED Annunciator
ANN-LED annunciators must
be in same room as FACP
ANN-LED Annunciators