Optional Modules and Devices
installation details. Refer to "ANN-BUS Options" on page 121 for programming information.
CAUTION:
!
DO NOT CONNECT A PRINTER OR PC TO THE FACP IF A GROUND FAULT (ZERO IMPED-
ANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE MAY RESULT.
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY WIRING.
Installation
Remote printers and PCs require separate primary power. Also required is the PRT/PK-CABLE
which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-CABLE to TB7 Ter-
minals 1 - 4 as illustrated in the following figure. Connect the DB9F connector to the printer or PC
serial EIA-232 port. If a nine-pin serial connector is not available on the printer or PC, use a DB25
adapter. Make certain that the DB25 adapter does not swap the Transmit and Receive lines. Apply
power to the FACP and printer or PC. Note that a ground fault (zero impedance to ground) may
occur on the FACP, dependent on the printer or PC being used, due to this connection. For this rea-
son, it is important that there be no preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming. Refer to
"Printer/PC" on page 134.
Printer Configuration
Refer to the documentation supplied with the printer for pertinent information about printer setup.
Set the printer's options as listed in the following table:
PC Configuration
The Windows-based PK-CD Programming Utility Kit contains a CD-ROM with on-line help file.
2.6.6 Annunciators

Legacy ACM-8RF Relay Control Module

The ACM-8RF module provides eight Form-C relays with contacts rated for 5 amps.
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
POSSIBLE EQUIPMENT DAMAGE
5 4 3 2 1
9 8 7 6
PRT/PK-CABLE
TX
RCV
DTR
GRND
ACS
RS-232 PC/PRINTER
XMT RCV DTR GRND
1 COMM 2
T
T
B
B
6
7
Figure 2.18 Serial Printer and Computer Connections
COMMUNICATION SETUP
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:
AUTOMATIC LINE FEED
AUTOMATIC CARRIAGE RETURN
Red
White
Green
Black
SLC
SLC
SHIELD
B+ A+ B- A-
B
A
T
B
8
LARGE
7
EVEN
1 STOP
2400/4800/9600
NO
NO
Installation
59