Chapter 3: Installation; Mounting Options; Backbox Installation - Fire-Lite Alarms FIRE COMMAND 25 Installation And Operating Instruction Manual

Voice evacuation
Table of Contents

Advertisement

Installation
CHAPTER 3
3.1

Mounting Options

The cabinet may be surface or semi-flush mounted. Semi-flush mounting
requires use of the FC-TR trim ring illustrated in Figure 3-2. The door is
removable during the installation period by opening and lifting it off the
hinges. The cabinet mounts using two key slots at the top of the backbox
and two additional 0.250" diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the
cabinet in a clean, dry, vibration-free area where extreme temperatures are
not encountered. The area should be readily accessible with sufficient
room to easily install and maintain the panel. Locate the top of the cabi-
net approximately five feet above the floor with the hinge mounting on
the left. Determine the number of conductors required for the devices to
be installed. Sufficient knockouts are provided for wiring convenience.
Select the appropriate knockout(s) and pull the required conductors into
the box. Note that there are no knockouts on the back of the cabinet. All
wiring should be in accordance with the National and/or Local codes for fire alarm systems.
3.2

Backbox Installation

Surface Mounting
Semi-flush Mounting Using Optional FC-TR Trim Ring
Technical Manuals Online! - http://www.tech-man.com
Installation
Open the door and lift the door off the pin hinges.
Mark and predrill holes for the top two backbox keyhole mounting bolts using the dimensions shown.
Install two upper fasteners in the wall with the screw heads protruding.
Using the upper 'keyholes', mount the backbox over the two screws.
Mark and drill the lower two holes.
Install the remaining fasteners and tighten all fasteners to complete backbox mounting.
Open Trim Ring hardware kit which contains six (6)
screws and six (6) drywall anchors.
Remove VECP cabinet door by sliding door upward
off pin style hinges.
Place FC-TR trim ring around VECP cabinet making
certain that the hinge cut-outs are on the left hand or
hinged side of the cabinet.
Making certain that the trim ring is placed around the
VECP cabinet maintaining an equal distance from all
four sides of the cabinet, mark the centers of all six
FC-TR mounting holes.
Remove the trim ring and drill the holes where
marked on the wall.
Install the six (6) supplied drywall anchors into the drilled holes.
Place the FC-TR trim ring around the VECP cabinet and secure in place using the six (6) supplied
screws.
firealarmresources.com
Document #50580
Rev. C
8/12/97
P/N 50580:C
VECP Cabinet
FIGURE 3-1:
FC-TR Trim Ring
FIGURE 3-2:
19