Zone Relay Module - 4XZMF (12V: 4412ZM)

The Zone Relay module provides Form-C contacts for the following:
• Relay #1 - Alarm Zone 1
• Relay #2 - Alarm Zone 2
• Relay #3 - Alarm Zone 3
• Relay #4 - Alarm Zone 4
• Relay #5 - System Alarm
• Relay #6 - System Trouble
Note: As a jumper option, Alarm Zone 1, 2, 3 & 4 can be made Silenceable.
Specifications
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30
VAC (resistive).

Remote Annunciator - RZA-4XF

The Remote Annunciator mounts on a standard single-gang box, and provides
LED indication of the following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• System Trouble LED (yellow)
A local trouble sounder and silence switch are also provided. All LED wiring
is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate. Slide-in paper labels permit an easy change of
zone information.
Note: The Remote Annunciator requires the use of an LED Interface Module as described below.

LED Interface Module - 4XLMF (12V: 4412LM)

The LED Interface Module supports the RZA-4XF Remote Annunciator
Module. Annunciator wiring is supervised for open conditions by this module.
The module mounts to the main board on the J8 option connector.
Specifications
Maximum voltage/current, each output: 27.6 V / 8 mA.
Outputs are power-limited.
MS-4412B/MS-4424B Instruction Manual PN 15125:G1 10/22/02