Setting Printer Options - Fire-Lite Alarms MS-9600LS Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Accessories
4.
Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to "ANN-BUS Options" on page 121).
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 131).
5.
Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.7). Only
one printer can be connected.
Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
Ambient Temperature: 32
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6"W x 7-3/4"H x 1-7/16"D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
PRN 6F Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN-6F prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the event
occurred. It provides 80 columns of data on standard 9" x 11" tractor-feed paper. This section con-
tains information on connecting a printer to the control panel and setting the printer options.
Connecting PRN-6F Printer
Remote printers require a primary AC power source. If required for the fire alarm system configu-
ration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power
source (battery backup). Since a secondary power source is not provided as a standard feature, a
separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency
power supply may be used, as long as it meets the power continuity requirements of NFPA 72.
Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable.
One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs
into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB-9 port on the ANN-
S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer
cable. Connect either a serial or parallel printer, but not both at the same time.

Setting Printer Options

Refer to the documentation supplied with the PRN-6F printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Font
LPI
ESC Character
Bidirectional Copy
CG-TAB
Country
Auto CR
Color Option
Formien
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
o
F to 120
Option
HS Draft
6 LPI
ESC
ON
Graphic
E-US ASCII
OFF
Not Installed
Lines
6LPI=60
Table 1.2 PRN-6F Setup Options
o
F (0
o
C to 49
o
C)
Setting
Option
CPI
Skip
Emulate
I/O
Buffer
Serial
Baud
Format
Protocol
Character Set
Product Description
Setting
10CPI
0.5
Epson FX-850
40K
9600 or 2400
7 Bit, Even, 1 Stop
XON/XOFF
Standard